Sharp AH-N45DP2 Service Manual page 18

Split system room air conditioners, indoor / outdoor units
Table of Contents

Advertisement

AH-N45DP2
AU-N45DP2
AH-N56DP2
AU-N56DP2
The room is not cooled at all
or not cooled.
The compressor does not operate.
Push the button "AUX." on
the indoor unit, for more than 5 sec.
Using a tester, measure voltage at
the terminals on the terminal board.
Is the voltage
between terminal "N" and
"1" of the terminal board the
power supply voltage ?
YES
The control circuit is normal.
The compressor may be defective.
The running capacitor may be
defective.
Refrigerant may be leaked.
The outdoor fan motor may be
defective.
The outdoor fan motor capacitor
may be defective.
Fig. 1 Temperature properties of indoor thermistors
K
100
Thermistor
Room temperature
80
Heat exchange
To measure the resistance, first remove
60
the connector as shown at right.
40
20
0
-10
0
10
NO
Measure resistances of TH1 and TH2.
Are the resistances
conformed Fig. 1 ?
YES
Replace the PWB ass'y with a new one.
18
Color
Connector
Yellow
No. 3 to 4
Orange
No. 1 to 2
Heat exchange thermistor
TH2 (orange)
25°C resistance 15 K
Room temperature
thermistor TH1 (yellow)
25°C resistance 10 K
20
30
40
Fig. 1
NO
Replace the thermistor ass'y
with a new one.
Room temperature
Heat exchange
thermistor TH1
thermistor TH2
CN4
1
4
Tester
Tester

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ah-n56dp2Au-n45dp2Au-n56dp2