Download Print this page

PVI Industries MAXIM 40 P 90A-MXG Specification

Packaged gas water heater

Advertisement

Quick Links

MODEL NUMBER
GPH Recovery at 40° to 120° F
GPH Recovery at 40° to 140° F
Input Btu/h
*
Minimum inlet flow gas pressure – " W.C.
A
Cold Inlet - NPT
B
Hot Outlet - NPT
C
Drain - NPT
D
I - Beam Skids
F
Overall Height
G
Flue Outlet Diameter
H
Gas Inlet - NPT
J
Motor HP 120 V, 1Ø, 60 Hz.
K
Motor Amps
L
Height to Outlet
M
Height to Inlet
Approx. Shipping Weight - lbs
Recoveries based on 83% thermal efficiency. ASHRAE 90.1 compliant.
Dimensions are in inches unless otherwise specified.
* The information presented is for natural gas 0.6 S.G. – For operation with propane (LP gas), consult the factory.
For standard and optional equipment, see form # PV 6141.
STANDARD GAS PRESSURE REQUIREMENTS:
SEE TABLE FOR MINIMUM PRESSURE BY MODEL NUMBER.
MAXIMUM STATIC INLET GAS PRESSURE: 14" W.C.
FOR GAS PRESSURES OUTSIDE OF THIS RANGE,
CONTACT YOUR PVI REPRESENTATIVE.
STANDARD ELECTRICAL REQUIREMENTS:
CONTROL VOLTAGE: 120V, 1Ø, 60 HZ., 2 AMPS
MOTOR VOLTAGE: 120V, 1Ø, 60 HZ.
SEE ABOVE CHART FOR BLOWER MOTOR AMPS
PV 6291 9/07
MAXIM • PACKAGED GAS WATER HEATER
®
POLYSHIELD
POLYMER-LINED STORAGE TANK
90 GALLON TANK SERIES
PVI INDUSTRIES, LLC
FORT WORTH, TEXAS 76111
(800) 784-8326 • www.pvi.com
40 P 90A-MXG
54 P 90A-MXG
500
670
400
540
399,000
540,000
4.5
4.0
2
2
2
2
1
1
3 x 34-1/2
3 x 34-1/2
64
72
7
8
3/4
1
1/3
1/3
8
8
53
61
28
36
1010
1130
VENTING REQUIREMENTS:
-.02" TO -.06" W.C. (NEGATIVE PRESSURE).
THE ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED UPON THE
VENT CONNECTION DIAMETER EXCLUSIVELY.
FOR PROPER VENT SIZING, CONSULT THE NATIONAL FUEL GAS CODE
PVI RESERVES THE RIGHT TO CHANGE THE DESIGN AND
1. Control Enclosure
2. ASME Temperature &
Pressure Relief Valve
3. 3" NPT Handhole
TYPE B VENTING
UNDER "FAN-ASSISTED".
SPECIFICATION WITHOUT NOTICE
Product is patented in the U.S., Canada, and Mexico.