Siemens RUGGEDCOM RM1224 Operating Instructions Manual page 33

Industrial remote communication remote networks
Table of Contents

Advertisement

The antenna socket for connecting the antenna is of the type SMA. The antenna used
should have an impedance of about 50 ohms.
Minimum clearance to the device
The device may only be operated when the distance between the device (or antenna) and
user is at least 20 cm.
Notes on lightning protection
Danger due to lightning strikes
Antennas installed outdoors must be within the area covered by a lightning protection
system. Make sure that all conducting systems entering from outdoors are protected by
lightning protection electrical bonding.
When implementing your lightning protection concept, make sure you adhere to the
requirements of the VDE 0182 or IEC 62305 standards.
Suitable lightning protectors are available in the range of accessories of RUGGEDCOM. For
more information, contact Siemens Customer Support.
Danger due to lightning strikes
Installing this lightning protector between an antenna and a RUGGEDCOM RM1224 is not
adequate protection against a lightning strike. Most lightening protectors only works within
the framework of a comprehensive lightning protection concept. If you have questions, ask
a qualified specialist company.
Note
The requirements of EN61000-4-5, "Surge Immunity Test" on power supply lines with 24
VDC are met only when a Blitzductor is used:
24 VDC: BVT AVD 24 type no. 918 422
Vendor: DEHN+SÖHNE GmbH+Co.KG, Hans Dehn Str. 1, Postfach 1640, D -
92306 Neumarkt, Germany
RUGGEDCOM RM1224
Operating Instructions, 10/2016, RC1260-EN-02
CAUTION
WARNING
Depending on the connector, an adapter cable is required to connect to SMA.
WARNING
Connecting up
3.6 Antennas
33

Advertisement

Table of Contents
loading

Table of Contents