Installation

2.1 Securing the housing

2.1
Securing the housing
Types of installation
For the device, you have the following options:
Strain relief for the cables
Regardless of the type of installation, make sure that there is suitable strain relief for the
connecting cable.
Shielding of cables
If cables are installed permanently, it is advisable to remove the insulation of the shielded
cable and to establish contact on the shield/PE conductor bar.
Permitted installation direction
Clearances
Keep to the minimum clearances to other components or to walls of a housing so that the
convection ventilation of the device is not blocked.
2.2

Wall mounting

Note
The wall mounting must be capable of supporting four times the weight of the device, but at
least 50 N. For information on the weight, refer to the section "Technical specifications
(Page 41)".
Requirement
There is a SIM card for the device.
18
Wall mounting (no ceiling mounting)
Installation on a DIN rail
Installing on the S7-300 standard rail
Installing on the S7-1500 standard rail
Vertical installation (ventilation openings at the top and bottom)
Below at least 10 cm
Above at least 10 cm
With an RM1224, a clearance of 5 cm must be maintained between the sides and
adjacent devices.
RUGGEDCOM RM1224
Operating Instructions, 10/2016, RC1260-EN-02