HONEYWELL EXCEL 5000 OPEN SYSTEM
GENERAL INFORMATION
left DIP switch
LonWorks
(USED = wall
service LED
module connected)
LonWorks
terminal assign-
service
right DIP switch
ment label
button
(USED = terminal
11 enabled)
W7754Kxxxx
UNUSED
ON
UNUSED
0345
WALL MOD.
DI2
230 Vac, 50/60 Hz
USED
USED
max. 5 VA unloaded
8 9 10 11 12
10A
2 A
+ -
1
2
3
4 5 6
7
131415
16
17
III II
5 3 4 2 1
L
LON
230 V
N
T7460 / T7560
terminals for hardwiring
to wall module and/or sensor(s)
removable LonWorks
terminal plug
digital output for low-voltage
PWM control of solid-state relay
Fig. 1. Top view of Excel 10 W7754 FCU Controller
(optional terminal cover removed)
All three models of the Excel 10 W7754 Fan Coil Unit (FCU)
Controller are equipped with a minimum of
three relays,
one LED digital output,
two digital inputs, and
two analog inputs.
Further, depending on the hardware requirements of your
specific application, you can choose from among models
equipped with the following additional features:
® U.S. Registered Trademark
Copyright © 2006 Honeywell Inc.
All Rights Reserved
D-71101 Schönaich
Made in Germany
triac
0.5 A
18
1920 2122
2324
2526
2A/M
I
N
L
230 V
OUT1 OUT2
230 Vac
relays
triacs
removable power
supply terminal plug
W7754K,P,Q FAN COIL UNIT
W7754K1001
230 Vac power supply
one triac output
one digital output, for the low-voltage Pulse-Width
Modulated (PWM) control of a solid-state relay
employed in high-current electrical reheat applications
three relays
W7754P1000
230 Vac power supply
four triac outputs
four relays
W7754Q1008
24 Vac power supply
four triac outputs
four relays
See also Table 1 on page 3 for a complete overview of
terminals and their functions.
fuse
BEFORE INSTALLATION
IMPORTANT
It is recommended that the controller be kept at room
temperature for at least 24 hours before applying
power; this is to allow the evaporation of any
condensation resulting from low shipping / storage
temperatures.
US requirement, only: This device must be installed
in a UL-listed enclosure offering adequate space to
maintain the segregation of line voltage field wiring
and Class 2 field wiring.
CAUTION
To avoid electrical shock or equipment damage, you
must switch OFF the power supply before attaching /
removing connections to/from any terminals.
Excel 10
CONTROLLERS
INSTALLATION INSTRUCTIONS
EN1B-0304GE51 R0306C

Advertisement

loading

Summary of Contents for Honeywell Excel 10

  • Page 1 (optional terminal cover removed) power; this is to allow the evaporation of any condensation resulting from low shipping / storage All three models of the Excel 10 W7754 Fan Coil Unit (FCU) temperatures. Controller are equipped with a minimum of •...
  • Page 2 EXCEL 10 W7754K,P,Q FAN COIL UNIT CONTROLLERS MOUNTING Wall/Ceiling Mounting/Dismounting The Excel 10 W7754 FCU Controller can be mounted on All models have the same dimensions (W x L x H = walls or ceilings in any desired orientation. In the case of 110 x 180 x 60 mm) (see Fig.
  • Page 3 Using Honeywell's LNS plug-in, you can configure the controller's triac outputs and relay outputs for a variety of different functions. E.g. the triac outputs can be configured for connection to either a floating drive or to a thermal actuator. Once the outputs have been configured, the corresponding devices can be directly connected to them.
  • Page 4 Wall Modules General Information The T7460 and T7560 Wall Modules can be used in con- junction with Excel 10 W7754 FCU Controllers to perform room temperature sensing, set-point adjustment, fan speed NOTE: All wiring must comply with applicable electrical manual override, and occupancy override. When hardwired to codes and ordinances.
  • Page 5 Deviations from this rule can result in improper The Excel 10 W7754 FCU Controller is equipped with a free- electrical contact. Local wiring codes may take precedence topology transceiver for communication on L ®...
  • Page 6 EXCEL 10 W7754K,P,Q FAN COIL UNIT CONTROLLERS Digital Inputs Hardware Limits for Excel 10 W7754Q1008 (24 Vac Power Supply) • Low signal: 0 V; high signal: 24 Vac The Excel 10 W7754 FCU Controller's digital inputs are • Maximum allowable continuous current for each suitable for connection with dry contacts, only.
  • Page 7 EXCEL 10 W7754K,P,Q FAN COIL UNIT CONTROLLERS Accessories Table 5. L Service LED Behaviors and Meanings ORKS Terminal Protection Cover LED blinking pattern meaning Defective device hard- Required for wall/ceiling mounting. Set of eight covers. ware. Suspect power • order no.: XAL_COV_L LED remains OFF after power-up.
  • Page 8 EXCEL 10 W7754K,P,Q FAN COIL UNIT CONTROLLERS Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37, Switzerland by its Authorized Representative: Automation and Control Solutions Honeywell GmbH Böblinger Straβe 17 D-71101 Schönaich...

This manual is also suitable for:

W7754kW7754pW7754qW7754k1001W7754q1008W7754p1000