Power wiring figure
■
Please make sure that when the unit is running, the input voltage is no less than 380V; if it is lower than 380V, the
unit may run abnormal.
Outdoor 1
L1 L2 L3 N
Ground Fault Interruptor
Circuit Breaker
Power source: 3N~, 380-400V, 50/60Hz
Indoor 1
L N
Ground Fault Interruptor
Circuit Breaker
Power source: 3N~, 380-400V, 50/60Hz
■
Indoor and outdoor use their individual power source.
■
All indoors use one power source.
■
Must install the leakage breaker and the over current breaker, or electric shock will occur.
Outdoor power source and power cable
Item
Power
source
Model
AV08NMSETA
3N~,
AV10NMSETA
380-400V,
50/60 Hz
AV12NMSETA
■
Power cable must be fixed firmly.
■
Each outdoor must be earthed well.
■
When power cable exceeds the range, thicken it appropriately.
Outdoor 2
L1 L2 L3 N
Ground Fault Interruptor
Circuit Breaker
Power source: 3N~, 380-400V, 50/60Hz
Indoor 2
L N
Ground Fault Interruptor
Circuit Breaker
Power source: 3N~, 380-400V, 50/60Hz
Power
Wire
cable
length
section
breaker (A)
(m)
(mm²)
6
60
10
60
10
60
39
39
Outdoor 3
L1 L2 L3 N
Ground Fault Interruptor
Circuit Breaker
Power source: 3N~, 380-400V, 50/60Hz
Indoor 3
L N
Ground Fault Interruptor
Circuit Breaker
Power source: 3N~, 380-400V, 50/60Hz
Rated current of
residual circuit
Circuit
breaker (A) Ground
fault interruptor (mA)
Response time (S)
40
40A 30mA below 0.1S
40
40A 30mA below 0.1S
40
40A 30mA below 0.1S
Ground wire
Section
Screw
(mm²)
3.5
M5
3.5
M5
3.5
M5