Download Print this page
Flanders 95% DOP Filter Alpha 95 Specification Sheet

Flanders 95% DOP Filter Alpha 95 Specification Sheet

95% dop filter

Advertisement

Quick Links

F O R E M O S T I N A I R F I LT R AT I O N
General
Flanders Alpha 95 filters are designed for use in
HVAC applications requiring cleaner air than is
possible with ASHRAE rated filters, but where
HEPA filtered air is not required. The filters are
rated at 95% efficiency on 0.30 micrometer
particles by the DOP test method. The Alpha 95
is rated MERV 17 per ASHRAE Standard 52.2.
Alpha 95 filters are identical in design and con-
struction to the Alpha Cell HEPA filters except that
the media is 95% efficient on 0.30 micrometer par-
ticles.
Installation Considerations
Alpha 95 filters should be installed in Flanders
leak tight Alpha HEPA frames or Surelock Side
Access HEPA Housings on the positive-pressure
side of the system fan to prevent air bypass.
Sureaire diffuser sections, air mixing baffles or
long transitions should be used if the bank is close
to the fan.
Installation of Flanders ASHRAE efficiency
prefilters upstream of the fan is recommended to
ensure economical Alpha 95 filter life.
Important Features
Minimum efficiency is 95% on 0.30 micrometer
particles.
Manufactured in a variety of wood and metal
frame types.
Available with a media pack with aluminum
separators or with a separatorless pack.
Available in a variety of sizes with either a gasket
or gel seal.
®
Standard Alpha 95 filters have 1.7 times the cfm
capacity of standard Alpha Cell 99.97% DOP HEPA
filters at the same clean pressure drop. They are
normally rated at 500 fpm so that filter banks with
95% DOP filters can be sized the same as
ASHRAE-rated filter banks.
Typical applications for Alpha 95 include:
• Hospitals
• Biomedical
• Pharmaceutical
• Biotechnology
• Genetic Research
• Universities
• Laboratories
• Food Processing
• Photo Processing
• Semiconductor Fabrication
• Industrial Processing Systems Product
Flanders Filters ~ Foremost in Air Filtration
Toll Free: 1-800-637-2803
Alpha 95
95% DOP Filter
Bulletin PB1400-1106
1

Advertisement

loading
Need help?

Need help?

Do you have a question about the 95% DOP Filter Alpha 95 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Flanders 95% DOP Filter Alpha 95

  • Page 1 F O R E M O S T I N A I R F I LT R AT I O N General Flanders Alpha 95 filters are designed for use in HVAC applications requiring cleaner air than is possible with ASHRAE rated filters, but where HEPA filtered air is not required.
  • Page 2 Frame Depth Filter Size & (Inches) Frame Depth Designator GG-F GC-F YY-F 11-1/2 YU-F GN-F CC-F Construction Flanders manufactures both conventional Separator Style and Pureform Separatorless 95 DOP filters. To make a Separator Style filter, the media is folded over corrugated aluminum sepa- rators with hemmed edges to separate the pleats in the filter pack.
  • Page 3 ALPHA 95 COMPONENT CHART 0 - 00J - W - 08 - 03 - IU - 12 - 00 - GG - F Hardware 0 = None T = Extractor Clips Efficiency 00J = 95% DOP Capacity/Pack Style C = Separator D = 4 inch Pureform F = 8 inch Pureform W = 11 inch Pureform...
  • Page 4 General 1.1 Alpha 95 filters shall be extended media (separator type) (Pureform type) filters as manufactured by Flanders. 1.2 Filter sizes, capacities and construction op- tions shall be as scheduled on the drawings. 1.3 Filters shall be (UL 900 Class 1)( UL Class 2) listed.

This manual is also suitable for:

Ffi alpha 95