Recharge the battery overnight and perform the self-test again. If the replace battery LED
is still on, the battery will need to be replaced.

7.5 LOAD LEVEL / BATTERY CAPACITY BAR GRAPH

When line voltage is normal, the 5-LED display shows the power drawn from the UPS by
load. The display indicates the percentage of the UPS's rated capacity. For example, if
three LEDs are lit, the load is drawing between 41% and 60% of the UPS's capacity. If the
UPS is overloaded, the overload LED lights and alarm sounds. When in back up mode,
the 5-LED display shows the percentage of the battery capacity. When only one LED
lights, the battery is in battery low situation and will shut down soon.

7.6 SHUTDOWN MODE

In shutdown mode the UPS stops supplying power to the load, waiting for return of utility
power. UPS will shut down when battery is too low to protect the life of battery. And if the
"Green mode" is set, UPS will shut down automatically if there is no utility power present.
This is normally done to preserve battery capacity after the graceful shutdown of protected
servers. The line LED (Green) will flash every 4 seconds to indicate shutdown mode. After
180 seconds, the LED (Green) will turn off.
Note: The "Green mode" of UPS can be set by UPSMON
.

7.7 COLD START

When the UPS is off and no utility power exists, the cold start feature enables the UPS to
start up and apply power to the loads from just UPS battery power. Press and hold the
"ON/TEST" button for 2 seconds to cold start the UPS
.
TPX Series UPS 700VA Operational Manual – 97673-000