Tool Has Broken Or Not Been Stored - DENTSPLY inLab MC X5 Operating Instructions Manual

Table of Contents

Advertisement

Dentsply Sirona
Operating Instructions inLab MC X5
64 78 759 D3608
D3608.201.01.07.02 10.2017
7.4.4

Tool has broken or not been stored

If a tool breaks during the machining process, it can no longer be stored
automatically; proceed as follows:
CAUTION
Risk of injury
A broken tool can be hot and sharp-edged.
➢ Wait until the tool is cooled.
➢ Use gloves to protect against injury.
1. Access the service mode for maintenance of the collet chuck in the
software and continue to follow the instructions of the software.
2. Remove the collet chuck, as described in the Section "Cleaning and
maintenance of the collet chuck / collet chuck change [ → 74]".
3. Remove the remainders of the broken tool from the collet chuck.
4. Clean the collet chuck and insert the collet chuck back, as described
in Section "Cleaning and maintenance of the collet chuck / collet
chuck change [ → 74]".
5. Continue to follow the instructions of the software.
7 Maintenance and cleaning
7.4 Maintenance for the tool mandrel
77