Fujitsu ETERNUS CS800 S6 User Manual page 83

Hide thumbs Also See for ETERNUS CS800 S6:
Table of Contents

Advertisement

6. Check if the rail will be fixed by pressing the left rail backwards.
7. Repeat this procedure to install the right rail.
Option
Fix each rail with one earthquake security screw M5 (5). The earthquake security screw has
to be tightened with max. 1Nm.
Figure 54: Mounting the server onto the rack rails
1. Fully extend the telescopic rails until they lock in place (1).
The telescopic rails must click into place so that they can no longer be moved.
2. At a slight angle, lower the server onto the rear mounting point on the telescopic rails
(2).
3. Fold down the server (3) while pressing the rails inwards to the server sides. Ensure
that all rack mounting bolts (6 or 8) are properly seated in the mounting points on
the telescopic rails and that the locking bars engage (4).
ETERNUS CS800
5.2 Installing the components in the rack
83