10.4

Outputs

Table 10- 7
Current output (Channel 1)
Description
Signal range
Resolution
Load
Time constant (adjustable)
Fault current
Measurement range (mA)
Lower fault current (mA)
Upper fault current (mA)
Customized fail-safe mode
Galvanic isolation
SITRANS F Ultrasonic flowmeters FST030 (HART)
Operating Instructions, 08/2017, A5E35971532-AC
Channels 3 and 4
Standard industrial signal cable with up to 3 twisted pairs with
overall screen can be connected between the transmitter and the
control system. Individual pair or overall screen is optional depend-
ing on user requirements.
Max. 24 V DC (active)
14 to 30 V DC (passive)
Channels 5 and 6 input (RTD)
Channels 5 and 6
-50 to 250°C (-58 to 482°F)
<0.1 mK
+/- 0.25 K (calibrated 4 wire)
25 VDC overvoltage
2, 3 or 4 wire
Channel 1
4 to 20 mA
0.4 μA
Ex i: <470 Ω (HART ≥ 230 Ω)
Non-Ex: <770 Ω (HART ≥ 230 Ω)
0.0 to 100 s
4 - 20 NAMUR
3.8 - 20.5
3.5
22.6
Last valid value
Lower fault current
Upper fault current
Fail-safe value
Current value
All inputs and outputs are galvanically isolated PELV circuits with 60 V DC isolation from
each other and ground.
Maximum test voltage: 500 V AC
4 - 20 US
4.0 - 20.8
3.75
22.6
Technical data
10.4 Outputs
115