ER ROR D ETE C TION
If you use a wireless remote control, the lamp
on the photo detector unit will output error codes
by way of blinking patterns.
If you use a wired remote control, error codes
will apper on the remote control display.
See the lamp blinking patterns and error codes
in the table.
An error display is displayed only during operation.
Troubleshooting with the indoor unit display
OPERATION indicator (green)
TIMER indicator (orange)
POWERFUL indicator (green)
Troubleshooting with the wired
remote control display (Option)
If an error occurs, the following display will be shown.
("Er" will appear in the set room temperature display.)
Error code
Display mode
( ) : Number of flashing
2015.07.07
Error display
OPERATION
TIMER
lamp
(green)
(orange)
(1)
(1)
(1)
(2)
(2)
(2)
(2)
(2)
(3)
(3)
(4)
(4)
(5)
(5)
(5)
(5)
(6)
(6)
: 0.5s ON / 0.5s OFF
(6)
: 0.1s ON / 0.1s OFF
(6)
Wired
remote
POWERFUL
Description
control
lamp
lamp
Error code
(green)
Serial communication error
(1)
Wired remote control
(2)
communication error
Check run unfinished
(5)
Unit number or Refrigerant circuit
address setting error
(1)
[Simultaneous Multi]
Indoor unit capacity error
(2)
Combination error
(3)
Connection unit number
error (indoor slave unit)
[Simultaneous Multi]
(4)
Connection unit number error
(indoor unit or branch unit)
[Flexible Multi]
Master unit, slave unit set-up
(7)
error [Simultaneous Multi]
Indoor unit PCB model
(2)
information error
Manual auto switch error
(5)
Room temp. sensor error
(1)
Indoor unit Heat Ex. Middle temp.
(2)
sensor error
Indoor unit fan motor error
(1)
Drain pump error
(3)
Damper error
(7)
Indoor unit error
(15)
Outdoor unit main PCB model
information error or
(2)
communication error
Inverter error
(3)
Active filter error, PFC circuit
(4)
error
Trip terminal L error
(5)
7
Error display
Wired
remote
OPERATION
TIMER
POWERFUL
control
lamp
lamp
lamp
Error code
(green)
(orange)
(green)
Display PCB microcomputers
(6)
(10)
communication error
Discharge temp. sensor error
(7)
(1)
Compressor temp. sensor error
(7)
(2)
Outdoor unit Heat Ex. liquid
(7)
(3)
temp. sensor error
Outdoor temp. sensor error
(7)
(4)
Suction Gas temp. sensor error
(7)
(5)
(7)
(6)
Heat sink temp. sensor error
(7)
(7)
(8)
(2)
Liquid pipe temp. sensor error
(8)
(3)
Current sensor error
(8)
(4)
(8)
(6)
Trip detection
(9)
(4)
Compressor rotor position
(9)
(5)
detection error (permanent stop)
Outdoor unit fan motor error
(9)
(7)
4-way valve error
(9)
(9)
Discharge temp. error
(10)
(1)
Compressor temp. error
(10)
(3)
High pressure error
(10)
(4)
Low pressure error
(10)
(5)
Branch boxes error
(13)
(2)
[Flexible Multi]
Description
2-way valve temp. sensor error
3-way valve temp. sensor error
Sub-cool Heat Ex. gas inlet
temp. sensor error
Sub-cool Heat Ex. gas outlet
temp. sensor error
Discharge pressure sensor
error
Suction pressure sensor error
High pressure switch error