Install the heatsink.
11.
IMPORTANT: Install all components with the same configuration that was used on the failed
system board.
Install all components removed from the failed system board.
12.
Install the access panel
13.
Install the power supplies
14.
Power up the server.
15.
After you replace the system board, you must re-enter the server serial number and the product ID.
During the server startup sequence, press the F9 key to access RBSU.
1.
Select the Advanced Options menu.
2.
Select Service Options.
3.
Select Serial Number. The following warning appears:
4.
Warning: The serial number should ONLY be modified by qualified service
personnel. This value should always match the serial number located on the
chassis.
Press the Enter key to clear the warning.
5.
Enter the serial number and press the Enter key.
6.
Select Product ID. The following warning appears:
7.
Warning: The Product ID should ONLY be modified by qualified service
personnel. This value should always match the Product ID located on the
chassis.
Enter the product ID and press the Enter key.
8.
Press the Esc key to close the menu.
9.
Press the Esc key to exit RBSU.
10.
Press the F10 key to confirm exiting RBSU. The server automatically reboots.
11.

150W PCIe power cable option

("Access
panel" on page 30).
("AC power
supply" on page 37).
Removal and replacement procedures 69