Fronius Primo 3.0-1 Service Manual page 132

Grid-connected inverter
Table of Contents

Advertisement

Available languages

Available languages

132
(4)
(3)
(1)
(2)
(2)
The device data unit of the new
1
RECERBO must also be broken off
and returned to Fronius with the faulty
RECERBO.
NOTE! If you forget to connect the
device data unit or do not connect
it correctly, the inverter will show
status code 482 on the display.
Connect the broken off device data unit
2
(4) to the inside of the new RECERBO
Fit the RECERBO holder (3) to the new
3
RECERBO
- feed it in from above
- press downwards
NOTE! All guide bolts and pins
must be properly engaged.
Insert the new RECERBO module
4
The RECERBO holder locking devices
5
(2) must be fully engaged in the
housing shell
Insert the external fan cable into the
6
cable guide (1)
Insert the Datamanager card, close the
7
inverter and place it in the wall bracket
(see "Replacing the Datamanager
card" and "Opening and closing the de-
vice" sections)

Advertisement