Scheduling A Holiday - Honeywell LCBS Applications Manual

Connect solution
Hide thumbs Also See for LCBS:
Table of Contents

Advertisement

impossible to provide minimum fresh air ventilation without supply fan moving air. During "standby" and "unoccupied"
periods, the supply fan operates in conjunction with a call for heating or cooling and ventilation is disabled, as we assume
that people are not in the building space.
LCBS Connect users can permit the supply fan to run only on a call for heating or cooling during "occupied" periods, but it
is discouraged and defies prevailing the building ventilation code. Further, cycling the fan on a call for heating or cooling
can degrade the life of the fan motor, fan belts, and associated fan accessories.
LCBS Connect controllers have the ability to control local equipment based on an eight (8) day scheduling strategy, seven
days of the week featuring four events per day and a "holiday" schedule featuring four events per day.
Let's get into some specific details.
There are four (4) programmable events that are available for each event.
Occupied. This indicates the beginning of a time period, associated with an "on" condition or observance of "occu-
pied" set points when building occupant typically occupy building zones.
Unoccupied. This indicates the beginning of a time period, associated with an "off" condition or observance of
"unoccupied" set points when building occupants typically leave the building.
Standby. This indicates the beginning of a time period, associated with observance of "standby" set points, were
ventilation and fan are controlled conforming to unoccupied control behavior. Using "standby" set points and pro-
cess can result in energy savings during traditional occupied hours. During the standby period, if an occupancy
sensor is assigned to the controlled zone, and it detects people in the controlled zone, occupied set points and
occupied ventilation practice is observed. If this occupancy sensor does not detect movement, unoccupied set
points and ventilation practice is observed. Tip: Use standby set points in infrequently occupied building zones
including meeting rooms and break rooms.
Available. This is a fourth condition indicating that a change of event state can be programmed, configured, exe-
cuted. This is also referred to as "un-configured."
How it works
Date and Time is available for each LCBS Connect controller. Each LCBS controller can support for events. For example,
assume that I open my store at 7:00 AM and close it at 7:00 PM Monday through Friday. My store is open at 7:00 AM and
closes at 1:00 PM on Saturday. I'm closed on Sunday. Find constructed table of required schedules below:
DAY
EVENT TYPE
MONDAY
OCCUPIED
TUESDAY
OCCUPIED
WEDNESDAY
OCCUPIED
THURSDAY
OCCUPIED
FRIDAY
OCCUPIED
SATURDAY
OCCUPIED
SUNDAY
AVAILABLE
Scheduling Summary
LCBS Connect controllers have a default schedule built into them. The LCBS Connect controller will work
when you pull them out of the box. The default schedule is 6:00 AM to 6:00 PM Monday through Sunday. If
you want to set up different occupancy schedules, it's a good idea to refer to appropriate documentation
form in your support package, print it out, and write out the schedules you want to implement. Go to LCBS Connect wall
module or LCBS Connect Remote User Interface and program desired times.

Scheduling a Holiday

LCBS Connect controllers support the following holiday scenarios for one event schedule. This will be improved in the
future, particularly when we implement "Cloud Based Scheduling":
Date specific: A good example of this is July 4 for our national holiday and December 25 for Christmas. This could be
obvious, but isn't intended to be insulting to the reader. July 4th never changes as a date, but the day of week does.
EVENT 1
TIME
EVENT TYPE
7:00AM
UNOCCUPIED
7:00AM
UNOCCUPIED
7:00AM
UNOCCUPIED
7:00AM
UNOCCUPIED
7:00AM
UNOCCUPIED
7:00AM
UNOCCUPIED
AVAILABLE
AVAILABLE
Table 1.
EVENT 2
TIME
EVENT TYPE
7:00PM
AVAILABLE
7:00PM
AVAILABLE
7:00PM
AVAILABLE
7:00PM
AVAILABLE
7:00PM
AVAILABLE
7:00PM
AVAILABLE
AVAILABLE
5
LCBS CONNECT SOLUTION
EVENT 3
EVENT 4
TIME
EVENT TYPE
AVAILABLE
AVAILABLE
AVAILABLE
AVAILABLE
AVAILABLE
AVAILABLE
31-00118EFS—01
TIME

Hide quick links:

Advertisement

Table of Contents
loading