en | Preparing Wiring
5

Preparing Wiring

4
Maximum cable distance in meters (feet) per minimum cable diameter
The following table identifies the recommended transmission distance (maximum) in meters
(feet), based on the specified wattage, per the minimum cable diameter (in mm²), when the
cable diameter is fixed and the maximum permitted power consumption for 24 VAC is 10%.
For example, for a device of 20 W and a minimum cable diameter of 1.0 mm², the
recommended transmission distance is 42 m (141 feet) from the transformer.
Models
Indoor
(ceiling)
Outdoor
Wire Gage
Note: Metric wire sizes are standard DIN sizes, ISO6722, mm².
Wire diameter (mm²)
1.0
1.5
2.5
4.0
2017.08 | 1.0 |
Prepare and install all wiring for 24 VAC, PoE+ (Cat5e/Cat6), alarms, and audio as
necessary. For 24 VAC, follow the recommendations for maximum cable distance and
wire gage.
Watts
20
42 m (141 ft)
30
28 m (94 ft)
1.0 mm²
1.5 mm²
68 m (225 ft)
45 m (150 ft)
Installation Manual
AUTODOME IP 5000i IR
2.5 mm²
4.0 mm²
109 m (358 ft)
275 m (905 ft)
72 m (238 ft)
183 m (603 ft)
AWG
18
16
14
12