Built-in unit

3.1.3.1

Permitted mounting positions

The mounting positions described below are permitted for the built-in unit. For information on
the maximum permissible ambient temperatures during operation, see section
"Environmental conditions (Page 213)".
Danger from high temperature of the enclosure if built-in unit is touched
Self-heating can cause the temperature of the built-in unit to exceed 70 °C during operation
at an ambient temperature > 45 °C.
If you want to operate the built-in unit at an ambient temperature > 45 °C, you will have to
install it in a Restricted Access Location (RAL) such as a lockable control cabinet.
● Standard mounting position: Vertical installation in horizontal format
In this mounting position, the device enclosure satisfies the requirements of a fire
protection enclosure.
1
SIMATIC IPC477D, IPC477D PRO
Operating Instructions, 11/2016, A5E31347228-AF
CAUTION
For temperature specifications, see section "Environmental conditions (Page 213)".
Mounting and connecting the device
3.1 Preparing for mounting
51