7. EXPLANATION OF PARAMETERS
Abbre-
Mode Page
viation
1
0
INP
1
OVF
Name and description
In-position (positioning finish) signal width
• This parameter selects the number of waiting
pulses on the deviation counter that output
the in-position signal.
• The standard value is the encoder pulse
irrespective of the electronic gear function or
the command multiplier setting.
INC-E, ABS-E
Incremental pulse multiplied by 4 is standard.
ABS-RⅡ, ABS-E.S1
Sensor absolute value (PS) is standard.
[Example]
When the parameter is set at 64 with a 2000
pulse encoder, the positioning complete
signal is output when the value falls in the
following range toward the target position:
64 × 1/(2000 × 4) × 360° = 2.88°
Excess deviation value
• When the deviation counter exceeds the
setting range, an OVF alarm occurs.
Standard
value
64
256
7-36
Setting
Unit
Remarks
range
pulse
1 to
Position control
(+/−)
32767
× 256
1 to
Position control
pulses
32767