Step
7
Calibrate the potentiometer.
Connect a multi meter set to ohms ( Ω ) to terminals TB4-35 & TB4-36.
Use a small allen wrench in the hole on the potentiometer actuator sleeve to turn the potentiometer.
Adjust the potentiometer to 500 Ω +/- 5 Ω.
Install the set screw.
When the potentiometer is set for 500 Ω tighten the set screw.
8
Replace the gasket.
9
Re-attach the top cover.
Page 4 of 5
Action
62-86-33-41