Honeywell Spyder PUB6438S Installation Instructions Manual

Honeywell Spyder PUB6438S Installation Instructions Manual

Spyder bacnet programmable, vav/unitary controllers
Hide thumbs Also See for Spyder PUB6438S:

Advertisement

®
Spyder
Programmable, VAV/Unitary Controllers
Controller
Programmable
Model
Type
PUB6438S
Unitary
PVB6436AS
VAV
PVB6438NS
VAV
Each controller communicates via an EIA-485 BACnet MS/TP network communications network, capable of baud rates between
9.6 and 115.2 kilobits.
Controllers are field-mountable to either a panel or a DIN rail.
SPECIFICATIONS
General Specifications
Rated Voltage: 20–30 Vac; 50/60 Hz
Power Consumption:
100 VA for controller and all connected loads (including the
actuator on model PVB6436AS).
Controller Only Load: 5 VA maximum; models PUB6438S
and PVB6438NS.
Controller and Actuator Load: 9 VA maximum; model
PVB6436AS.
®
BACnet
Table 1. Controller configurations.
Universal
Digital
Inputs
Inputs
(UI)
6
6
6
PRODUCT DESCRIPTION
The PUB6438S, PVB6436AS and PVB6438NS controllers are
part of the Spyder family. The three controllers are BACnet
MS/TP network devices designed to control HVAC equipment.
These controllers provide many options and advanced system
features that allow state-of-the-art commercial building
control. Each controller is programmable and configurable
through software.
These controllers are for use in VAV (Variable Air Volume) and
Unitary HVAC control applications. Each controller contains a
host micro controller to run the main HVAC application and a
second micro controller for BACnet MS/TP network
communications. Each controller has flexible, universal inputs
for external sensors, digital inputs, and a combination of
analog and digital Triac outputs. The three models are
described in Table 1. The photo to the left is the model
PVB6436AS, which includes the actuator.
Analog
Outputs
(DI)
(AO)
4
3
4
3
4
3
External Sensors Power Output: 20 Vdc ±10% @ 75 mA
maximum.
VAV Operating & Storage Temperature Ambient Rating
(models PVB6436AS and PVB6438NS):
Minimum 32 ºF (0 ºC); Maximum 122 ºF (50 ºC)
Unitary Operating & Storage Temperature Ambient Rating
(model PUB6438S):
Minimum -40 ºF (-40 ºC); Maximum 150 ºF (65.5 ºC)
Relative Humidity: 5% to 95% non-condensing
LED: Provides status for normal operation, controller down-
load process, alarms, manual mode, and error conditions
BEFORE INSTALLATION
The controller is available in three models (see Table 1).
INSTALLATION INSTRUCTIONS
Velocity
Digital
Pressure
Outputs
Sensor
(DO)
(Microbridge)
8
NO
6
YES
8
YES
Series 60
Floating
Actuator
NO
YES
NO
62-0310-01

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell Spyder PUB6438S

  • Page 1 ® ® Spyder BACnet Programmable, VAV/Unitary Controllers INSTALLATION INSTRUCTIONS PRODUCT DESCRIPTION The PUB6438S, PVB6436AS and PVB6438NS controllers are part of the Spyder family. The three controllers are BACnet MS/TP network devices designed to control HVAC equipment. These controllers provide many options and advanced system features that allow state-of-the-art commercial building control.
  • Page 2: Installation

    SPYDER® BACNET® PROGRAMMABLE, VAV/UNITARY CONTROLLERS Review the power, input, and output specifications on page 1 reduce the rotation travel. Each “hash mark” indi- before installing the controller. cator on the bracket represents approximately — Hardware driven by Triac outputs must have a minimum 6.5°...
  • Page 3: Mount Controller

    SPYDER® BACNET® PROGRAMMABLE, VAV/UNITARY CONTROLLERS Tighten the two bolts on the centering clamp Before mounting the actuator onto the VAV box damper shaft, (8 mm wrench; 70.8–88.5 lb-in. [8–10 Nm] torque). determine the following: g. When the actuator closes, the damper rotates CCW 1.
  • Page 4: Panel Mounting

    SPYDER® BACNET® PROGRAMMABLE, VAV/UNITARY CONTROLLERS PANEL MOUNTING HOLE (4X) 29/64 IN. (12) PVB6438NS PUB6438S 2 2 2 2 2 2 2 2 3 2 2 2 2 2 2 2 2 3 5-3/4 1 2 3 4 5 6 7 8 0 1 2 3 4 5 6 7 8 0 1 2 3 4 5 6 7 8 0 1 2 3 4 5 6 7 8 0...
  • Page 5 SPYDER® BACNET® PROGRAMMABLE, VAV/UNITARY CONTROLLERS pneumatic controls) is recommended for the high — Do not connect the universal input COM pressure line (marked as ) connected to the air terminals, analog output COM terminals or the flow pickup. digital input/output COM terminals to earth —...
  • Page 6: Setting The Ms/Tp Mac Address

    200 pF per meter (60 pF per foot). Foil or braided shields are Setting the Device Instance Number acceptable. The Honeywell tested and recommended MS/TP cable is Honeywell Cable 3322 (18 AWG, 1-Pair, Shielded, The Device Instance Number must be unique across the Plenum cable), alternatively Honeywell Cable 3251 (22 AWG,...
  • Page 7: Termination Resistors

    SPYDER® BACNET® PROGRAMMABLE, VAV/UNITARY CONTROLLERS e. Select OK Capacitive coupling is caused by placing MS/TP cabling close 3. Right Click on the Spyder Controller and select Actions to lines carrying higher voltage. The shield should be > Write Device Instance to complete the update grounded on only one end of the MS/TP segment (typically the router end).
  • Page 8: Controller Replacement (Pvb6438Ns)

    • Press straight down to firmly seat it. Automation and Control Solutions Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9 customer.honeywell.com ® U.S. Registered Trademark © 2009 Honeywell International Inc. 62-0310—01 M.S. 08-09...

This manual is also suitable for:

Spyder pvb6436asSpyder pvb6438ns