Programming SITRANS LR560

Quick Start Wizard
• See
Quick Start Wizard via AMS Device Manager
• See

Activating SITRANS LR560

Power up the device. At initial startup, SITRANS LR560 will not begin measurements and all
blocks will be Out of Service until the instrument has been configured either locally or from a
remote location.
• Completing the Quick Start Wizard or writing any configuration parameter via the local
user interface causes the device to begin measuring. The Resource Block (RES) and
Level Transducer Block (LTB) will move to Automatic mode.
• AIFB 1 and AIFB 2 will remain Out of Service (as displayed on the LCD). These blocks can
only be configured and scheduled using a network configuration tool. For more details,
see System Integration in manual
(7ML19985MP01)
• A transition screen showing first the Siemens logo and then the current firmware revision
is displayed while the first measurement is being processed.
• The first time the device is configured you will be prompted to select a language (English,
German, French, Spanish or Chinese).

Local Display Interface (LDI)

Modify parameters using the LDI push buttons.
(Siemens infrared handheld programmer can be ordered
separately: [Part No. 7ML1930-1BK]).

The LCD Display

Measurement mode display
1
2
3
4
7
6
1)
Fault present indicators
When a fault is present the fault code and an error message are
S: 0 LOE
displayed in the text area (7), and a service-required icon appears in the
device status location (8)
1)
Press
or
to switch.
Page EN-10
on page 12.
Foundation Fieldbus for Level Instruments
(normal operation)
( ((
1 – toggle indicator
2 – identifies which AIFB is source of displayed value
3 – measured value (level, space, or distance)
4 – units
5 – bar graph indicates level
6 – text area displays status messages
7 – device status indicator
5
SITRANS LR560 (FF)
on page 17.
1)
for AIFB 1 or AIFB 2
7ML19985XR82