Power Supply - Honeywell F58G Product Data

Commercial duct mounted electronic air cleaner
Hide thumbs Also See for F58G:
Table of Contents

Advertisement

F58G COMMERCIAL DUCT MOUNTED ELECTRONIC AIR CLEANER1
Tools and Equipment
Troubleshooting the electronic air cleaner requires:
• Needlenose pliers for stringing ionizer wires and inserting
edge connectors.
• Ohmmeter.
Test Button
When pushed, the Test button shorts from collector voltage to
ground. The resulting arcing sound indicates that high voltage
is being supplied to the collector. The solid state power supply
controls current flow to the collector. The CHECK indicator
activates when the Test button is held down.
CHECK Indicator
The CHECK indicator activates to indicate the following
problems:
• Excessive dirt loading.
• Partial shorting of collector.
• Continuous ionizer or collector arcing.
• Power supply failure.
REPLACE STATUS
INDICATION
CIRCUIT CARD.
68-0233
START
MAKE SURE ELECTRONIC
CELLS ARE CLEAN, DRY
AND PROPERLY INSTALLED.
MAKE SURE PREFILTER
IS INSTALLED.
TURN ON ELECTRONIC AIR
CLEANER AND SYSTEM
POWER.
OFF
CHECK ON LIGHT.
ON
PUSH TEST BUTTON AND
NO
LISTEN FOR SNAPPING
SOUND.
YES
DEPRESS AND HOLD DOWN
OFF
TEST BUTTON. CHECK
INDICATOR SHOULD COME
ON AFTER ABOUT
40 SECONDS.
ON
ELECTRONIC AIR
CLEANER IS OK.
Fig. 11. Troubleshooting the F58G.
• Excessive ionizer current.
• Any condition causing a major reduction in high voltage.

Power Supply

WARNING
Electric Shock Hazard.
Can cause personal injury.
Turn off power before accessing the power supply.
The solid state power supply can be replaced when
troubleshooting indicates a problem.
Troubleshooting Procedure
The electronic air cleaner troubleshooting diagram shows how
to quickly isolate a problem in the air cleaner. Although an
ohmmeter is needed in some steps, the primary diagnostic
tools are the status indicators and the Test button. See
Fig. 11.
TO USE THIS CHART:
1.
FOLLOW THE STEPS IN ORDER; DO NOT SKIP AROUND.
2.
EACH TIME YOU ISOLATE AND FIX A PROBLEM, GO BACK TO START.
3.
REPEAT ALL THE STEPS UNTIL THE AIR CLEANER CHECKS OUT OK.
WARNING
ELECTRIC SHOCK RISK
THESE SERVICING INSTRUCTIONS ARE FOR USE BY QUALIFIED
PERSONNEL ONLY. TO REDUCE RISK OF ELECTRIC SHOCK, DO NOT
PERFORM ANY SERVICING OTHER THAN CONTAINED IN THE OPERATING
INSTRUCTIONS UNLESS YOU ARE QUALIFIED TO DO SO.
PUSH TEST BUTTON AND
YES
LISTEN FOR SNAPPING
SOUND.
NO
TURN OFF AIR CLEANER AND
REMOVE CELLS ONLY (NOT
PREFILTER). TURN ON
AIR CLEANER.
OFF
CHECK ON LIGHT.
ON
INSPECT CELL(S) FOR:
• BENT COLLECTOR PLATES
• BROKEN IONIZER WIRES
• DIRT ON INSULATORS
• DAMAGED IONIZER OR
COLLECTOR CONTACT
TABS
YES
REPAIR OR
NO
REPLACE CELL(S).
WITH OHMMETER, CHECK
FOR SHORT BETWEEN:
• CELL FRAME AND IONIZER
SECTION
• CELL FRAME AND
COLLECTOR SECTION
CELL
SHORTED
INFINITE
REPLACE CELL.
RESISTANCE
CELL OK.
10
REPLACE STATUS
INDICATION CIRCUIT CARD.
WARNING
THIS STEP EXPOSES
DANGEROUSLY HIGH
VOLTAGE. ONLY A
QUALIFIED SERVICE
TECHNICIAN SHOULD
ATTEMPT THIS STEP.
OPEN POWER SUPPLY TRAY.
CHECK FOR CORRECT INPUT
VOLTAGE ACROSS QUICK
CONNECT TERMINALS ON
POWER SUPPLY TRANSFORMER.
NO
YES
FIX
WIRING.
REPLACE
POWER
SUPPLY.
M13460