How To Remove Upper Half Exhaust Frame - GE MS-6001B Maintenance Instructions Manual

Gas turbines with dln-1 combustion systems gas only
Hide thumbs Also See for MS-6001B:
Table of Contents

Advertisement

Major Inspection — Disassembly Procedures
8. Jack the turbine case to exhaust frame flange (position 2) to 0.004 0.001 in. Record all dial indica-
tor readings. Recheck all jacks for snugness.
9. Jack the compressor discharge to turbine casing flange (position 3) to 0.002 –0.003 in. Record all
dial indicator readings. Recheck all jacks for snugness.
10. Jack the aft or compressor case to compressor discharge flange (position 4) to 0.002–0.003 in. Re-
cord all dial indicators. Recheck all jacks for snugness.
11. Jack the forward compressor case to aft compressor case flange (position 5 if applicable) to
0.002–0.003 in. Record all dial indicators. Recheck all jacks for snugness.
Note: To prevent out-of-roundness occurring all casings should not be un-
bolted prior to removal. This is very tempting to do when running more
than one (1) shift operation with only one (1) shift crane coverage.
It is permissible to remove every other bolt on the horizontal joint and
every other bolt in the vertical joint except for the top six casings should
not be replaced without being bolted. Again, every other bolt on the
horizontal and vertical joint with six on top is permissible.
Casings should be removed in the following sequence; exhaust frame,
forward compressor case, inlet case, turbine case and compressor dis-
charge. Reinstallation is in the reverse order, i.e. compressor discharge
case, turbine case, etc.
Operation 8 — How to Remove Upper Half Exhaust Frame
Note: The rail beam, trolley hoist and spreader bar are applicable to vertical
exhaust stack configurations only. On side exhaust stack configura-
tions the cowl cover on the exhaust plenum is removed for access to the
exhaust frame for removal using an overhead crane and normal
rigging.
1. Install the rail beam, trolley hoist, and spreader bar used for exhaust frame and turbine casing re-
moval inside the exhaust duct transition piece.
2. Disconnect and remove as necessary all instrumentation tubing for wheelspace thermocouples and
pressures inside the inner barrel tunnel.
3. Remove the left and right side outer horizontal joint insulating packs and identify for location.
4. Remove the outer insulating pack on the upper half aft vertical flange.
5. Remove the upper half vertical bolting between turbine case and exhaust frame.
MI-D-8
CAUTION
Do not, under any circumstances remove the mechanical
support jacks or dial indicators until all upper half casings
have been reinstalled and bolted up.
Inspection and Maintenance — GEK 107048

Advertisement

Table of Contents
loading

Table of Contents