SIMATIC
Industrial PC
SIMATIC IPC227E
Operating Instructions
11/2016
A5E35782395-AB
___________________
Preface
___________________
Overview
___________________
Safety instructions
___________________
Installing and connecting the
device
___________________
Commissioning the device
and device functions
___________________
Expanding and assigning
parameters to the device
___________________
Maintaining and repairing the
device
___________________
Technical specifications
___________________
Technical support
___________________
Markings and symbols
___________________
List of abbreviations
1
2
3
4
5
6
7
A
B
C

Advertisement

Table of Contents
loading

Summary of Contents for Siemens simatic ipc227e

  • Page 1 Preface ___________________ Overview ___________________ SIMATIC Safety instructions ___________________ Installing and connecting the device Industrial PC SIMATIC IPC227E ___________________ Commissioning the device and device functions ___________________ Expanding and assigning parameters to the device Operating Instructions ___________________ Maintaining and repairing the device...
  • Page 2: Legal Information

    Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Preface

    The documentation is supplied with the IPC in multiple languages as PDF on the USB stick supplied in the documentation package. Conventions The terms "PC" and "device" are sometimes used to refer to the SIMATIC IPC227E in this documentation. In these operating instructions, "Windows Embedded Standard" is also used as a standard term for "Windows Embedded Standard 7".
  • Page 4 Preface SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 5: Table Of Contents

    Upright mounting ........................37 Connecting the device ......................38 3.3.1 Notes on connecting ....................... 38 3.3.2 Connecting the protective conductor ..................40 3.3.3 Connecting the power supply ....................41 3.3.4 Connect device to networks ....................43 SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 6 Installing drivers and software ....................82 6.4.4 Installing updates ........................83 6.4.4.1 Updating the operating system ....................83 6.4.4.2 Installing or updating application programs and drivers ............83 6.4.5 Backing up data ........................83 Recycling and disposal ......................84 SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 7 Exit menu ..........................124 7.6.5 Default BIOS Setup entries ....................125 7.6.6 BIOS update ......................... 128 7.6.7 Alarm, error and system messages ..................129 Functional scope in Windows ....................130 7.7.1 Windows Embedded Standard 7 ..................130 SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 8 Markings and symbols ........................... 137 Overview ..........................137 Safety ........................... 137 Operator controls ......................... 137 Certificates, approvals and markings ................... 138 Interfaces ..........................139 List of abbreviations ..........................141 Glossary ..............................145 Index ..............................153 SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 9: Overview

    Overview Product description SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 10 Overview 1.1 Product description SIMATIC IPC227E provides high-level industrial functionality. ● Compact design ● High degree of ruggedness ● Maintenance-free operation possible SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 11: Structure Of The Devices

    The front view on the left is the standard mounting position, side view on the right. ① Cooling fins ② LED display Bottom view ① Protective conductor connection ② Memory card slot ③ Ports SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 12: Views Of The Pcie Device Version

    1.2.2 Views of the PCIe device version Front view and side view The front view on the left is the standard mounting position, side view on the right. ① Cooling fins ② LED display SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 13 Overview 1.2 Structure of the devices Bottom view ① Protective conductor connection ② Memory card slot ③ Ports SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 14: Interfaces And Operator Controls Of The Basic Device

    USB 2.0 port, high current ⑦ Serial interface, 9-pin (optional) • RS 232 • RS 422 • RS-485 ⑧ DisplayPort connection ⑨ RJ45 Ethernet connection 1 for 10/100/1000 Mbps ⑩ RJ45 Ethernet connection 2 for 10/100/1000 Mbps SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 15: Interfaces And Operator Controls Pcie Device Version

    • RS 232 • RS 422 • RS-485 ⑧ DisplayPort connection ⑨ Slot for a PCIe x1 card ⑩ RJ45 Ethernet connection 1 for 10/100/1000 Mbps ⑪ RJ45 Ethernet connection 2 for 10/100/1000 Mbps SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 16: Status Displays

    You can find information on the individual LEDs in the section Output register user LED L1/L2/L3 (read/write, address 404Eh) (Page 117). Example programs for controlling the LEDs on Windows operating systems are available on the Customer Support page of Siemens Industry Automation and Drive Technologies. (http://www.siemens.com/automation/service&support) SIMATIC IPC227E...
  • Page 17: Accessories

    Additional accessories can be found on the Internet at: ● Expansion components and accessories (http://www.automation.siemens.com/mcms/pc-based-automation/en/industrial- pc/expansion_components_accessories) ● Industry Mall (https://mall.industry.siemens.com) CFast cards Note CFast cards can only be replaced with cards of the same manufacturing versions This device supports only SIMATIC IPC CFast cards with version 02 or higher.
  • Page 18 Overview 1.3 Accessories Graphics adapter ● DisplayPort DVI adapter ● DisplayPort VGA adapter SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 19: Safety Instructions

    • Observe the safety and installation instructions for the expansion cards. • If in doubt, install the device in an enclosure that is compliant with sections 4.6 and 4.7.3 of the IEC/UL/EN/DIN-EN 60950-1 standard. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 20 Radiation exposure in excess of the specified immunity limits can impair device functions, result in malfunctions and therefore injuries or damages. Read the information on immunity to RF radiation in the technical specifications. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 21 In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept. Siemens’ products and solutions only form one element of such a concept. Customer is responsible to prevent unauthorized access to its plants, systems, machines and networks.
  • Page 22 2.1 General safety instructions Disclaimer for third-party software updates This product includes third-party software. Siemens AG only provides a warranty for updates/patches of the third-party software, if these have been distributed as part of a Siemens software update service contract or officially released by Siemens AG. Otherwise, updates/patches are undertaken at your own risk.
  • Page 23: Notes On Use

    Validate the correct functioning of the plant to avoid functional restrictions. Note Use in an industrial environment without additional protective measures This device was designed for use in a normal industrial environment according to IEC 60721-3-3. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 24 Safety instructions 2.2 Notes on use SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 25: Installing And Connecting The Device

    The device may be damaged. Do not dispose of the original packaging. Pack the device during transportation and storage. 5. Check the contents of the packaging and any accessories you may have ordered for completeness and damage. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 26 7. Please keep the enclosed documentation in a safe place. It belongs to the device. You need the documentation when you commission the device for the first time. 8. Write down the identification data of the device. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 27: Identification Data Of The Device

    When you order a replacement device, remove all the storage media from your device, for example SSD. Insert the storage media into the replacement device. 2. Transfer the Windows "Product Key" from the COA label. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 28 The COA label is only attached to the rear of the device containing a Windows Embedded Standard 7 or Windows 7 operating system. ● COA label of a device with Windows Embedded Standard 7 operating system ● COA label of a device with Windows 7 operating system SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 29: Permitted Mounting Positions

    "Technical specifications (Page 99)" section. Ensure that the following clearances measurements to another component or to a wall of a housing are complied with: ● Below the device: ≥ 100 mm ● Above the device: ≥ 50 mm SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 30: Installing The Cable Strain Relief

    Secure the strain relief on the left and right respective- ly with an M3x8 setscrew. Secure the connection ca- bles with cable ties to the cable strain relief. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 31: Installing Ethernet Connector Strain Relief

    Insert the metal plate of the Ethernet connector strain relief into the sec- ond and third to the last notch. Fasten the Ethernet con- nector strain relief with 2 setscrews. Secure the Ethernet con- nector with cable ties. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 32: Installing The Atex Cable Strain Relief

    ● The device is approved for operation in closed rooms only. ● For installation in a cabinet, observe the SIMATIC setup guidelines (http://support.automation.siemens.com/WW/view/de/1064706) as well as the relevant DIN/VDE requirements or the applicable country-specific regulations. ● When the device is used in the area of Industrial Control Equipment in accordance with UL508, note that the device is classified as "Open Type".
  • Page 33 The position of the interface side is determined by the mounting of the mounting bracket. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 34 Screw, ∅ 4-5 mm, 40 mm long • mounting elements used Plasterboard, Toggle plug, ∅ 12 mm, 50 mm long min. 13 mm thick Metal, Screw M4 × 15 • min. 2 mm thick M4 nut • SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 35: Mounting On A Standard Rail

    Mounting on a standard rail Mounting on a standard rail is suitable for horizontal and vertical mounting of the device. Requirement ● A SIEMENS 35 mm standard rail TH35-15 conforming to EN 60715:2001 The standard rail is mounted. ● A standard rail bracket The standard rail bracket and two screws are included in the order variant "Standard rail...
  • Page 36: Wall Mounting

    2 screws. Place the device with the mount- ing brackets onto the mounting surface. Mark the fixing holes. Drill the fixing holes. Insert the anchors in the drilled holes. Screw on the device. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 37: Upright Mounting

    2 screws. Place the device with the mount- ing brackets onto the mounting surface. Mark the fixing holes. Drill the fixing holes. Insert the anchors in the drilled holes. Screw on the device. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 38: Connecting The Device

    • Only connect I/O devices which are approved for industrial applications in accordance with EN 61000-6-2 and IEC 61000-6-2. • I/O devices that are not hotplug-capable may only be connected after the device has been disconnected from the power supply. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 39 Regenerative feedback of voltage to ground by a connected or installed component can damage the device. Connected or built-in I/Os, for example, a USB drive, are not permitted to supply any voltage to the device. Regenerative feedback is generally not permitted. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 40: Connecting The Protective Conductor

    M4 thread (see part labeled). Connect the protective conductor to the protec- tive conductor connection of the cabinet or the plant in which the device is installed. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 41: Connecting The Power Supply

    ● You are using the supplied terminal. ● A two-core cable with a cable cross-section of 0.75 mm to 2.5 mm for the 24 VDC connection. ● A slotted screwdriver with a 3mm blade. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 42 Installing and connecting the device 3.3 Connecting the device Procedure Switch off the 24 VDC power supply. Connect the cores of the power supply. Insert the terminal at the indicated position. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 43: Connect Device To Networks

    Field & Control level. Information on this can be found on the SIMATIC NET Manual Collection CD. The software package and the documentation are not included in the scope of delivery. Additional information You can find additional information on the Internet at: Technical Support (https://support.industry.siemens.com) SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 44 Installing and connecting the device 3.3 Connecting the device SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 45: Commissioning The Device And Device Functions

    ● The protective conductor is connected. ● The connection cables are plugged in correctly. ● The following hardware is available for initial commissioning: – One USB keyboard – One USB mouse – A monitor/display SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 46: Switching On The Device

    6. If the device is connected with a SIMATIC Industrial Flat Panel, the setup of the SIMATIC PDT (Panel Drivers Tool) is started automatically after operating system installation (see next section). The installation of the operating system is complete. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 47: Windows Security Center

    ● Real-time protection (Windows 7 only): Windows Defender displays warnings if spyware or possibly unwanted software is installed or executed on the computer. You will also receive a warning if programs attempt to modify important Windows settings. Configure the Security Center according to your requirements. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 48: Advanced Device Functions

    SIMATIC IPC DiagMonitor is available on CD (not included in the scope of delivery). This monitoring software comprises: ● The software for the stations to be monitored. ● A library for creating user-specific applications. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 49: Temperature Monitoring/Display

    A watchdog alarm is retained after a restart and is reset and logged by the DiagBase or DiagMonitor software. The watchdog configuration is retained in the process. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 50: Battery Monitoring

    SIMATIC DiagBase and SIMATIC DiagMonitor diagnostic software determines the status of the backup battery. When the first warning level is reached, the battery for buffering CMOS data still has a remaining service life of at least one month. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 51: Enhanced Write Filter

    Write-protect drive C: enable ewfmgr c: -commitanddisable Write-protect drive C: disable (modified data is transferred) ewfmgr c: -commit Modified files on drive C: Accept ewfmgr c: Display information about the EWF drive ewfmgr /h Display help SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 52 Start > Control Panel > Date and Time, remove the check mark from the "Automatically adjust clock for daylight saving changes" check box. 2. Save the change you have made with and then reboot the system. ewfmgr c: -commit SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 53: File-Based Write Filter

    Display the current FBWF status fbwfmgr /enable Enable FBWF after the next startup fbwfmgr /commit c: \Test.txt Write to protected files Adding/removing elements in the exception list: fbwfmgr /addexclusion C: \Test.txt Add file • SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 54: Buffer Memory Nvram

    A memory window with a maximum size of 512 KB can be displayed by means of PCI address register. The base address is initialized via the BIOS (see section "Input/output address areas (Page 116)"). A corresponding function is implemented there for using the NVRAM under WinAC RTX. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 55: Expanding And Assigning Parameters To The Device

    • You can not lay down the rear panel because of the drive's connecting cable. • The rear panel can only be completely removed after disconnecting the connection plug. • Read the information in section "Replacing the drive of a basic device (Page 68)". SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 56 • Ensure that the rear panel does not fall. • Remove the connection plug from the drive. Procedure - closing the device To close the device, carry out the steps for opening the device in the reverse order. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 57: Installing A Pcie Module

    Make sure that the maximum permissible ambient temperature of the PCIe-x1 module is specified accordingly. Requirement ● The device is opened. ● A plug-in card ● A T10 screwdriver SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 58 Insert the plug-in card. Ensure that the connector of the plug-in card adapter has been inserted correctly into the slot on the motherboard. Tighten the screw. Insert the plug-in card holder into the housing. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 59 5.2 Installing a PCIe module Turn the pressure piece on card holder if necessary to adjust the bracket to the height of the plug- in card. Push the pressure piece against the plug-in card Tighten the screw SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 60: Installing And Removing Cfast Cards

    • Always insert a CFast card version 02 or higher. • Always replace a CFast card with a card of the same or higher version. • The production version can be found on the CFast card (see marking). SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 61 3. Close and lock the cover. Removal Remove the CFast card from the memory slot by pushing it in until it is ejected by about 5 mm (ball-point pen mechanism). Proceed in reverse order. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 62 Expanding and assigning parameters to the device 5.3 Installing and removing CFast cards SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 63: Maintaining And Repairing The Device

    Make sure you take precautionary measures even when you open the device, for example, when opening device doors, device covers or the housing cover. For more information, refer to the chapter "ESD Guideline (Page 90)" SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 64 Tools to open the device, see section "Opening the device". You can make repairs on the device with the following tools: ● T20 screwdriver for protective conductor connection and enclosure ● T10 screwdriver for all of the remaining screws SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 65: Installing And Removing Hardware

    • Label the battery container "Used batteries and rechargeable batteries". Requirement ● The device is disconnected from the power supply. ● The device is opened. ● The drive has been removed, see section "Replacing the drive". SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 66 Remove also the Velcro fastener on the cover. PCIe device version Pull out the connector. Remove the battery with the attached Velcro from the Velcro fastener on the enclosure. Remove also the Velcro fastener on the enclosure. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 67 3. Replace the Velcro on the cover/enclosure. When sticking on the new Velcro, pay attention to the position mark on the enclosure. 4. Attach the replacement battery with the Velcro to the Velcro on the cover/enclosure. See also Open the device (Page 55) SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 68: Replacing The Drive Of A Basic Device

    ● A T10 screwdriver Procedure - removing Pull out the connection plug. Lay down the device's rear panel including the drive. Remove the indicated screws. Remove the drive rack and take out the SSD. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 69 If you install a hard disk drive instead of the SSD, you will need to use insulating film between the hard disk drive and drive rack, as indicated in the following figure. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 70: Replacing A Drive For The Pcie Device Version

    Read the information in section "Repair information (Page 63)". Requirement ● The device is opened. ● A T10 screwdriver Procedure - removing Take the plug-in card holder out of the housing. Lift up and remove the cover. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 71 Loosen the 4 marked screws of the drive on the support plate. Remove the drive with insulating film (only for HDD) from the sup- port plate. Procedure - installation Proceed in reverse order. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 72: Installing The Software

    The supplied USB stick contains the documentation, hardware drivers and updates. In Windows, these contents are available via a menu. Restore function If you have ordered IPC277E with operating system, the supplied USB stick contains the Restore function. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 73: Restoring The Delivery State

    4. To boot from the USB stick, select the Boot Manager. 5. Select the USB stick in the Boot Manager and confirm the entry. 6. Select the Restore function and confirm the entry. 7. Follow the on-screen instructions. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 74 ● "Delivery state": The delivery state is completely restored. ● "Administrator Basic": The data storage medium is partitioned as in the delivery state: – Windows is installed. – No settings from Siemens AG are contained. – No additional drivers or software are installed. SIMATIC IPC227E...
  • Page 75: Installation Of Windows 7

    • Check the data and time in the BIOS setup, "Main" menu and correct the displayed time if necessary. 8. Now follow the instructions of the installation program "Install Windows". You will find additional information in the operating system manual. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 76 English. You can change the language of the operating system after the installation. You can find information on this in section: "Setting up the language selection by means of the Multilanguage User Interface (MUI) (Page 80)". SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 77: Windows With Ahci Controller

    Read the information in the section "Information for systems with data storage medium controller". Drive options For display of additional functions that you can use to set up the data carriers, (advanced) see figure "Windows installation window "Drive options (advanced)"". SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 78 Deleting a partition Extend Changing the partition size Format Formatting a partition Creating new partitions Identification for error messages, for example, if the data carrier was not format- ted in the required "NTFS" format. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 79 1. Connect the USB stick with the controller driver to the device. 2. Start the "Install Windows" installation program as described above. 3. Select "Load Drivers" in the Windows installation window. 4. Select the respective driver on the USB stick. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 80: Setting Up The Language Selection By Means Of The Multilanguage User Interface (Mui)

    "Start > Control Panel > Clock, Language, and Region > Regional and Language Options" 2. You can make the required changes in the "Administrative" tab. You copy the settings by clicking the respective button. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 81 3. Click the "Install/uninstall languages" button and make the required changes. The following languages can be installed at a later time: Language Windows German English French Italian Spanish Chinese (Hong Kong) Chinese (simplified) Chinese (Taiwan) Japanese Russian SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 82: Partitioning Data Media

    6. Open the folder with the driver data by clicking on the link next to "Driver path". 7. Start the setup program in this folder. Note For a new installation of Windows operating systems, the chipset driver must be installed before all other drivers, if required. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 83: Installing Updates

    (images). The SIMATIC IPC Image & Partition Creator can be ordered using the Siemens online ordering system (https://mall.industry.siemens.com). For more information about SIMATIC IPC Image & Partition Creator, refer to its product documentation.
  • Page 84: Recycling And Disposal

    The devices described in these operating instructions can be recycled thanks to their low level of pollutants. Observe the local statutory requirements for environmentally sound recycling and disposal of your old devices. Alternatively, you can use a certified disposal service company. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 85: Technical Specifications

    EC declaration of conformity, UL approval for Canada/USA (http://support.automation.siemens.com/WW/view/en/48958203). DIN ISO 9001 certificate The Siemens quality management system for all production processes (development, production and sales) meets the requirements of DIN ISO 9001:2000. This has been certified by DQS (the German society for the certification of quality management systems).
  • Page 86 When used in environments according to class I, division 2 (see above), the device must be mounted in an enclosure that corresponds to at least IP54 according to EN 60529. ATEX and IECEx Cat3G devices for use in Zone 2. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 87: Fcc (Usa) And Ices (Canada) Compliance

    This product meets the requirements of EN 61000-6-3 Generic standards - Emission standard for residential, commercial and light-industrial environments. This product meets the requirements of the standard EN 61000-6-3 Generic standards - Emission standard for residential, commercial and light-industrial environments. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 88 ● ABS American Bureau of Shipping (USA) ● BV Bureau Vertias (France) ● DNV Det Norske Veritas (Norway) ● GL Germanische Lloyd ● LR Lloyds Register of Shipping ● Class NK Nippon Kaiji Kyokai (Japan) SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 89: Directives And Declarations

    The device is designed for the following areas of application corresponding to the CE marking: Scope of application Requirements for Interference emission Immunity to interfer- ence Industrial area EN 61000-6-4:2007 +A1:2011 EN 61000-6-2:2005 Residential and commercial areas EN 61000-6-3:2007 +A1:2011 EN 61000-6-1:2007 and small businesses SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 90: Esd Guideline

    The consequences are incalculable and range from unforeseeable malfunctions to a total failure of the machine or system. Avoid touching components directly. Make sure that persons, the workstation and the packaging are properly grounded. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 91 There is no equipotential bonding without grounding. An electrostatic charge is not discharged and may damage the ESD. Protect yourself against discharge of static electricity. When working with electrostatic sensitive devices, make sure that the person and the workplace are properly grounded. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 92 This way, the discharge energy does not reach and damage the sensitive components. – Discharge your body electrostatically before you take a measurement at a module. Do so by touching grounded metallic parts. Always use grounded measuring instruments. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 93: Dimension Drawings

    Technical specifications 7.3 Dimension drawings Dimension drawings 7.3.1 Dimension drawing basic device Mounting on a standard rail all dimensions in mm SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 94 Technical specifications 7.3 Dimension drawings Wall mounting all dimensions in mm SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 95 Technical specifications 7.3 Dimension drawings Upright mounting all dimensions in mm SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 96: Dimension Drawing Pcie Device Version

    Technical specifications 7.3 Dimension drawings 7.3.2 Dimension drawing PCIe device version Mounting on a standard rail all dimensions in mm SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 97 Technical specifications 7.3 Dimension drawings Wall mounting all dimensions in mm SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 98 Technical specifications 7.3 Dimension drawings Upright mounting all dimensions in mm SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 99: Technical Data

    3 V/m, 2 … 2.7 GHz, 80% AM according to IEC 61000-4-3 10 V, 10 KHz … 80 MHz, 80% AM according to IEC 61000-4-6 Magnetic field 100 A/m, RMS value 50/60 Hz in accordance with IEC 61000-4-8 SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 100 Up to 512 MB, shared memory Resolution, graphics memory DisplayPort resolution: • 640 × 480 pixels to 2560 × 1600 pixels up to 512 MB, graphics memory is taken from the main • memory, dynamic UMA SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 101 Teaming can be set and initiated in the configuration interface. In teaming operation, jumbo frames, e.g. for the camera application, are not supported Teaming is not possible in connection with Windows 10. See also Permitted mounting positions (Page 29) SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 102: Ambient Conditions

    Barometric pressure 1080 to 795 hPa, corresponds to an elevation of - Operation • 1000 to 2000 m Storage/transport • 1080 to 660 hPa, corresponds to an elevation of - 1000 to 3500 m SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 103 • Impact resistance Tested in accordance with IEC 60068-2-27 Operation Without hard drive: 150 m/s , 11 ms • With hard disk: 50 m/s , 30 ms • Storage/transport 250 m/s , 6 ms SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 104: Shipbuilding

    May amount to maximum 1.2 A for up to 100 ms at start-stop torque of device Note Device can overheat! The power supply cannot make unlimited power available. The auxiliary components consume energy and produce heat. The device may overheat. The auxiliary components will be damaged. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 105: Direct Current Supply (Dc)

    Power consumption (at 24 V rated voltage) Basic device with Intel Celeron N2807 13 W Basic device with Intel Celeron N2930 15 W USB expansion See section "Power requirements of the com- ponents" Expansion PCIe SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 106: Hardware Descriptions

    BIOS Setup RS 232 • RS 485/RS 422 • CFast External CFast card External 4 USB channels 3 × USB 2.0 1 × USB 3.0 Ethernet External 2 x RJ45 10/100/1000 Mbps DisplayPort External DP SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 107: Serial Interface

    Pin assignment RS422 Short description Meaning Transmit data - (O) for full-duplex mode Transmit data + (O) for full-duplex mode Receive data + (I) for full-duplex mode Receive data - (I) for full-duplex mode Signal ground SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 108 Technical specifications 7.5 Hardware descriptions Pin assignment RS485 Short description Meaning Data- Transmit / receive data - (I/O) for half-duplex mode Data+ Transmit / receive data+ (I/O) for half-duplex mode Signal ground SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 109: Cfast

    LED Output (not connected) PC10 Reserved Input/Output (not connected) PC11 Reserved Input/Output (not connected) PC12 Reserved Input/Output (not connected) PC13 Device Power (3.3V) PC14 Device Power (3.3V) PC15 Device GND PC16 Device GND PC17 Card Detect Out SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 110: Usb 2.0 Port

    + 5 V (fused) Output Data channel USB2 Input / output Data channel USB2 Input / output Ground – Data channel USB3 Input Data channel USB3 Input Ground – Data channel USB3 Output Data channel USB3 Output SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 111: Displayport

    Output Ground ML_Lane3- DP data 3- Output CONFIG1 CAD Cable Adapter Detect Input CONFIG2 Ground (PullDown) AUX_CH+ Auxiliary channel+ Bidirectional Ground AUX_CH- Auxiliary channel- Bidirectional Hot Plug Detect Input Ground DP_PWR +3.3V (fused) Output SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 112: Ethernet Port

    BI_DD+ Bidirectional data D+, input/output BI_DD– Bidirectional data D–, input/output Short description Meaning LED 1 Off: 10 Mbps Lit green: 100 Mbps Lit orange: 1000 Mbps LED 2 Lit orange: Connection established Flashes: Activity SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 113: Internal Interfaces

    REFCLK- Reference clock (differential pair, Lane 0 pair) PETn0 Transmitter differential Ground pair, Lane 0 Ground PERp0 Receiver differential pair, Lane 0 PRSNT2# Hot-plug presence detect PERn0 Receiver differential pair, Lane 0 Ground Ground SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 114: System Resources

    PS/2 keyboard controller emulation ISA exclusive IRQ2 Interrupt controller 2 ISA exclusive IRQ3 COM2 IRQ4 COM1 IRQ5 Free IRQ6 Reserved IRQ7 Free IRQ8 Realtime clock ISA exclusive IRQ9 ACPI-SCI (system control interrupt) IRQ10 ISA exclusive SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 115 IRQ19 PCI Express Port 4 PCI exclusive IRQ20 USB EHCI controller PCI shared USB XHCI controller IRQ21 Trusted Execution Engine PCI exclusive IRQ22 SATA AHCI controller PCI exclusive IRQ23 HD audio controller PCI exclusive SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 116: Input/Output Address Areas

    210 ms / 4 s 340 ms / 6 s 460 ms / 8 s 590 ms / 16 s 710 ms / 32 s 840 ms / 48 s 960 ms / 64 s SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 117: Watchdog Trigger Register (Read Only, Address 066H)

    LED L2 / SF lit red LED L2 / SF lit yellow LED L3 / Maint dark (default) LED L3 / Maint lit red LED L3 / Maint lit yellow xxxx xxxx Reserved (read/write) SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 118: Battery Status Register (Read-Only, Address 50Ch)

    NVRAM address register PCI register address: PCI register content: Length of the memory area NVRAM base address regis- NVRAM memory address (default setting) 9060 0000h Address is assigned dynamically 80000 h (depending on device configura- tion) SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 119: Bios Description

    Setup parameters may not be included, depending on your order. The interface of your BIOS Setup can deviate from the figures in this document. You can find a detailed description of the BIOS on the Support website under Entry ID 92189178. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 120: Opening The Bios Selection Menu

    Configuration settings to start the device in Secure Boot mode. The only software modules loaded are those that are known to be safe for the BIOS or the operating system. Start BIOS Setup via Setup Configuration Utility SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 121 Technical specifications 7.6 BIOS description Buttons Function BIOS Update Update BIOS from USB memory stick MEBx Intel Management Engine AMT configuration Available as of Windows 8 or later SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 122: Structure Of The Bios Setup Menu

    Determine boot options, e.g., boot order Exit Save and exit (see Exit menu) The menus always have the same structure. The figure below shows an example for the "Main" menu. Device-specific information is shown blurred. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 123 Short help texts on the currently selected setup parame- ters are displayed in the center right-hand area. ⑤ Key assignment The key assignment for navigation in the BIOS Setup is found in the footer. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 124: Exit Menu

    Save the BIOS Setup settings as user-specific profile. • Save Custom Defaults The currently configured Setup parameters are saved as a custom profile (see also "Load Custom Defaults"). Discard Changes All changes are discarded. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 125: Default Bios Setup Entries

    Enabled Base I/O address Interrupt IRQ3 Transceiver Mode RS232 On-board Ethernet 1 Enabled Ethernet 1 Address 00:1B:1B:41:42:7B (exam- ple) On-board Ethernet 2 Enabled Ethernet 2 Address 00:1B:1B:0A:85:10 (exam- ple) Only for devices with COM2 SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 126 3. Enter "Exit" and confirm this with the ENTER key or close the command window. The IPC can now be set to "Hibernate" via the Start menu. The IPC is started up again when you touch the screen. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 127 Quick Boot Enabled Quiet Boot Enabled Network Stack Disabled PXE Boot to LAN Disabled Add Boot Options Auto USB Boot Enabled EFI Device First Disabled Legacy / Boot Device Priority Normal Boot Menu Standard SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 128: Bios Update

    There may be several reboots after a BIOS update. These reboots are initiated by the Management Engine (ME). The reboots are required by the ME to adapt itself to the changes of the BIOS update. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 129: Alarm, Error And System Messages

    Check the CMOS clock. Keyboard error Field PG: Internal keyboard defective and no external • keyboard connected Other devices: Keyboard defective or not connected • PLD configuration failed Programming of the PLC on the motherboard has failed. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 130: Functional Scope In Windows

    Available Printing Utilities and Management Available Available Registry Filter Available Available Remote Assistance Available Available Remote Client Available Available Remote Desktop Available Available SIMATIC IPC DiagBase Available, V1.5 Available, V1.5 Speech Available Not available SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 131 Note the licensing agreements for Windows Embedded Standard 7. Additional information on language selection is available in the section "Setting up the language selection by means of the Multilanguage User Interface (MUI) (Page 80)". SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 132 Technical specifications 7.7 Functional scope in Windows SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 133: Technical Support

    You can find additional information and support for the products described on the Internet at the following addresses: ● Technical support (https://support.industry.siemens.com) ● Support request form (http://www.siemens.com/automation/support-request) ● After Sales Information System SIMATIC IPC/PG (http://www.siemens.com/asis) ● SIMATIC Documentation Collection (http://www.siemens.com/simatic-tech-doku-portal) ● Your local representative (http://www.automation.siemens.com/mcms/aspa-db/en/Pages/default.aspx) ●...
  • Page 134: Troubleshooting

    Wrong time and/or date on the 1. Open the BIOS Setup. 2. Set the time or date. Although the BIOS setting is The backup battery is dead. Replace the backup battery. OK, the time and data are still wrong SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 135: Notes On The Use Of Third-Party Modules

    Different pin assignment • being used was the cause of the fault. Replace the thrid- party module with a Siemens module or contact the module supplier. If the device still crashes, contact your technical support team. Insufficient output of an external Use a higher capacity power supply •...
  • Page 136 Technical support A.3 Notes on the use of third-party modules SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 137: Markings And Symbols

    Opening for Kensington lock opening Attention ESD (Electrostatic sensitive Warning of hot surface device) Operator controls Symbol Meaning Symbol Meaning On/off switch, without electrical isola- Eject CD/DVD tion On/off switch, without electrical isola- tion SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 138: Certificates, Approvals And Markings

    CE markings for European countries Marking of Federal Communications Commission for the USA EFUP (Environment Friendly Use Approved for Korea Period) marking for China Test mark of the Underwriters La- Disposal information, observe the boratories local regulations. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 139: Interfaces

    DVI-D interface Line In LAN interface, not approved for con- Line Out necting WAN or telephone Serial port Microphone input USB port Universal Audio Jack USB 2.0 high-speed port Headphone output USB 3.0 super-speed port SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 140 Markings and symbols B.5 Interfaces SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 141: List Of Abbreviations

    Clear To Send Clear to send Direct Current DC current Data Carrier Detect Data carrier signal detection Direct Memory Access Disk Operating System DisplayPort Deutsche Gesellschaft zur Zertifi- zierung von Qualitätsmanagement SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 142 Mean Time Between Failures Multilanguage User Interface Language localization in Windows NTFS New Technology File System NVRAM Non Volatile Random Access Non-volatile data memory. Data memory is Memory retained without external power supply. Optical Disk Drive SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 143 Static RAM Solid State Drive Thin-Film-Transistor Transmit Data Data transfer signal UEFI Unified Extensible Firmware Inter- face Underwriters Laboratories Inc. US organization for testing and certification according to national or binational standards. Universal Serial Bus SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 144 Intel technology which provides a virtual, closed environment. VT-d Virtualization Technology for Di- Enables the direct assignment of a device rected I/O (e.g. network adapter) to a virtual device. Watchdog Program monitoring with error detection and alarming. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 145: Glossary

    EC directives such as the EMC Directive. CFast The faster SATA protocol is used with the CFast standard for memory cards based on CompactFlash. The connectors on these cards are not compatible with a classic CompactFlash card. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 146 The data are stored in a configuration file and enable the operating system to load the correct device drivers and configure the correct device parameters. . If changes are made to the hardware configuration, the user can change entries in the configuration file using the SETUP program. . SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 147 10/100/1000 Mbps. Execute Disable Capability Hardware implementation that prevents mutual memory accesses by programs and applications. It is only effective when all relevant system components, such as processors, operating systems and applications are supported. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 148 Intel Active Management Technology This technology permits diagnostics, management and remote control of PCs. It is only effective when all relevant system components, such as processors, operating systems and applications are supported. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 149 Conventional drives can be used as USB devices. License key The license key represents the electronic license stamp of a license. Siemens AG issues a license key for each software that is protected by a license. License key USB flash drive The license key USB flash drive contains the authorizations or license keys required to enable protected SIMATIC software.
  • Page 150 Recovery function of the USB stick Contains the tools for configuring hard disks and the Windows operating system. Reset Hardware reset: Reset/restart of the PC using a button/switch. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 151 This design makes SSDs more rugged, provides shorter access times, low energy consumption and rapid data transfer. STEP 7 Programming software for the creation of user programs for SIMATIC S7 controllers. Troubleshooting Error cause, cause analysis, remedy SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 152 Wake on Local area network. This function allows the PC to be started via the LAN interface. Warm restart The restart of a computer after a program was aborted. The operating system is loaded and restarted again. The CTRL+ ALT+ DEL hotkey can be used to initiate a warm restart. SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 153: Index

    Connecting EU Declaration of Conformity, 85 Network, 43 EWF (Enhanced Write Filter), 51 Peripherals, 38 Expansion slot, 100 Protective conductor, 40 Creating an image, 83 Factory state, 73 FBWF (File Based Write Filter), 53 SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 154 Limitation of liability, 64 PROFINET, 43, 105 Protection class, 99 Protective conductor, 40 Connecting, 40 Protective measure Marine approval, 88 Static electricity, 92 Marking EU Declaration of Conformity, 85 Memory medium, 100 Messages On the screen, 129 SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 155 Tools, 64 Trigger register Watchdog, 117 UL approval, 86 Updates Application programs and drives, 83 Operating system, 83, 83 Upright mounting, 37, 95, 98 USB, 106 USB 2.0 Port, 110 USB 3.0 Interface, 110 SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...
  • Page 156 Index SIMATIC IPC227E Operating Instructions, 11/2016, A5E35782395-AB...

Table of Contents