Siemens RUGGEDCOM RX1400 Installation Manual page 60

Hide thumbs Also See for RUGGEDCOM RX1400:
Table of Contents

Advertisement

Chapter 6
Certification
Test
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-9
IEC 61000-4-11
IEC 61000-4-16
IEC 61000-4-17
IEC 61000-4-18
IEC 61000-4-29
IEC 60255-5
a
Siemens-specified severity levels
EMC Immunity Type Tests per IEEE 1613
NOTE
The RUGGEDCOM RX1400 meets Class 1 requirements for copper ports, which allows for temporary
communication loss.
Test
IEEE 1613
50
Description
Induced (Conducted) RFI
Magnetic Field
Pulse Magnetic Field
Voltage Dips & Interrupts
Mains Frequency Voltage
Ripple on DC Power Supply
Damped Oscillatory Wave
Voltage Dips and Interrupts
Dielectric Strength
HV Impulse
Description
HV Impulse
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Enclosure Ports
Enclosure Ports
AC Power Ports
Signal Ports
DC Power Ports
DC Power Ports
Slow Damped
DC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
Signal Ports
Installation Guide
Test Levels
± 2 kV Line-to-Line
± 2 kV Line-to-Earth
± 1 kV Line-to-Line
± 4 kV Line-to-Earth
± 2 kV Line-to-Line
10 V
100 A/m Continuous
1000 A/m for 1 s
300 A/m
30% for 0.5 Cycles
60% for 5 Cycles
100% for 250 Cycles
30 V Continuous
300 V for 1s
10%
2.5 kV Common
100 kHz or 1 MHz
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
2 kV
5 kV
Test Levels
5 kV
EMC and Environmental Type Tests
RUGGEDCOM RX1400
Severity
Levels
3
4
3
5
4
4
3
3

Hide quick links: