Serial Ports - Siemens RUGGEDCOM RX1400 Installation Manual

Hide thumbs Also See for RUGGEDCOM RX1400:
Table of Contents

Advertisement

RUGGEDCOM RX1400
Installation Guide
IMPORTANT!
Only use SFP transceivers approved by Siemens for RUGGEDCOM products. Siemens accepts no liability
as a result of performance issues related in whole or in part to third-party components.
SFP Transceiver
RUGGEDCOM SFP1121-1FX2A
RUGGEDCOM SFP1132-1BX10R
RUGGEDCOM SFP1132-1BX10T
RUGGEDCOM SFP1132-1BX40R
RUGGEDCOM SFP1132-1BX40T
RUGGEDCOM SFP1122-1SX
RUGGEDCOM SFP1132-1LX10
RUGGEDCOM SFP1132-1LX25
RUGGEDCOM SFP1132-1LX40
RUGGEDCOM SFP1132-1LX70
RUGGEDCOM SFP1132-1LX100
a
MM = Multi-Mode, SM = Single-Mode
Section 3.3

Serial Ports

The RUGGEDCOM RX1400 supports two serial ports with female DB9 connectors, which can be run in RS-232,
RS-485 or RS-422 mode. For technical specifications, refer to
The following is the pin-out description for DB9 serial ports:
Serial DB9 Port
Figure 17: Serial DB9 Port Pin Configuration
Serial Ports
Order Code
6GK6000-8FE50-0AA0
6GK6000-8FB51-0AA0
6GK6000-8FB52-0AA0
6GK6000-8FB53-0AA0
6GK6000-8FB54-0AA0
6GK6000-8FG51-0AA0
6GK6000-8FG52-0AA0
6GK6000-8FG53-0AA0
6GK6000-8FG57-0AA0
6GK6000-8FG54-0AA0
6GK6000-8FG55-0AA0
5
1
9
6
Speed
Mode
(Mbit/s)
100
MM
1000
SM
1000
SM
1000
SM
1000
SM
1000
MM
1000
SM
1000
SM
1000
SM
1000
SM
1000
SM
Section 4.4, "Serial Port
Pin
RS-232
1
Reserved (Do Not Connect)
b
2
RX
b
3
TX
4
Reserved (Do Not Connect)
5
Common (Isolated) Ground
6
Reserved (Do Not Connect)
7
RTS
8
CTS
Communication Ports
a
Nominal Distance (km)
2
10
10
40
40
0.5
10
25
40
70
100
Specifications".
Mode
RS-422
RS-485
RX-
TX-
RX-/TX-
TX+
RX+/TX+
RX+
Chapter 3
27

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents