Honeywell 7847i-E Installation And Setup Manual page 26

Intranet communication modules
Hide thumbs Also See for 7847i-E:
Table of Contents

Advertisement

7847i-E Installation and Setup Guide
PROMPTS
Restore Zn2 Y/N
39
(Y)_
Delay Zn2 (secs)
40
(00)_
Rpt Zn2 ONLY if
41
Armed (N)_
If Lynx Panic is enabled, then skip to Prompt 46: "Rpt Zn3 ONLY if Armed."
Zn3 Trigger Type
42
(V+)_
Invert Zn3 Y/N
43
(N)_
Restore Zn3 Y/N
44
(Y)_
Delay Zn3 (secs)
45
(00)
Rpt Zn3 ONLY if
46
Armed (N)_
Zn4 Trigger Type
47
(V+)_
48
Invert Zn4 Y/N
(N)_
49
Restore Zn4 Y/N
(Y)_
Delay Zn4 (secs)
50
(00)
Rpt Zn4 ONLY if
51
Armed (N)_
Zn5 Trigger Type
52
(V+)_
Invert Zn5 Y/N
53
(N)_
Restore Zn5 Y/N
54
(Y)_
Delay Zn5 (secs)
55
(00)_
3-14
4204/
ZONE
ENTRY
2-4204
TRIG.
2-
4204
only
2-
4204
only
2-
4204
only
OPTIONS
[Y], [N]
Enables restore reporting for zone 2.
[01-15]
Defines the reporting delay in seconds for zone 2.
UL: Must be 00
[00]=no delay
[Y], [N]
Reports alarms on zone 2 ONLY if the conditional
zone (zone 7 in zone trigger mode; zone 4 in 4204
mode; zone 8 in 2-4204 mode) is triggered (armed).
If [N], always reports alarms on zone 2.
Selects the triggering method for this zone input.
• (EOLR)
Press the [space] key to scroll through choices.
• (V+)
UL: V+ must be set as inverted and V- as non-
• (V–)
inverted
Inverts the alarm and normal states of the zone 3
[Y], [N]
trigger; otherwise uses normal input signal.
[Y], [N]
Enables restore reporting for zone 3.
[01-15]
Defines the reporting delay in seconds for zone 3.
UL: Must be 00
[00] = no delay
[Y], [N]
Reports alarms on zone 3 ONLY if the conditional
zone (zone 7 in zone trigger mode; zone 4 in 4204
mode; zone 8 in 2-4204 mode) is triggered (armed).
If [N], always reports alarms on zone 3.
4204 mode: If any zone is programmed to "Report
Only if Armed," skip to Prompt 57: "Enable Zn6."
• (EOLR)
Selects the triggering method for this zone input.
• (V+)
Press the [space] key to scroll through choices.
• (V–)
UL: V+ must be set as inverted and V- as non-
inverted
[Y], [N]
Inverts the alarm and normal states of the zone 4
trigger; otherwise uses normal input signal.
[Y], [N]
Enables restore reporting for zone 4.
[01-15]
Defines the reporting delay in seconds for zone 4.
UL: Must be 00
[00] = no delay
[Y], [N]
Reports alarms on zone 4 ONLY if the conditional
zone (zone 7 in zone trigger mode; zone 8 in 2-
4204 mode) is triggered (armed).
If [N], always reports alarms on zone 4.
Selects the triggering method for this zone input.
• (EOLR)
• (V+)
Press the [space] key to scroll through choices.
• (V–)
UL: V+ must be set as inverted and V- as non-
inverted
[Y], [N]
Inverts the alarm and normal states of the zone 5
trigger; otherwise uses normal input signal.
[Y], [N]
Enables restore reporting for zone 5.
[01-15]
Defines the reporting delay in seconds for zone 5.
UL: Must be 00
[00] = no delay
DESCRIPTION