Honeywell 7847i-E Installation And Setup Manual page 15

Intranet communication modules
Hide thumbs Also See for 7847i-E:
Table of Contents

Advertisement

PROMPTS
Enter Password
6
Verify Password
7
Exit Prog. Mode?
8
(Y/N)_
Device Mode
9
(ECP)_
CS IP:
10
255.255.255.255
CS Port:
11
(80)
Alarm Delivery:
12
Only One CS IP_
Secondary CS IP:
13
255.255.255.255
Second CS Port:
14
(80)
IP2 Supervision
15
30 Day_
ENTRY
OPTIONS
[0-9, A-F, N, S,
T, X, Y]
[0-9, A-F, N, S,
T, X, Y]
[Y], [N]
[ESC]
• ECP
• Zone Triggers
• 4204 Emu
• Two 4204s
12 digit:
xxx.xxx.xxx.xxx
[80]
[Only One CS IP]
[Fail to CS IP2]
12 digit:
xxx.xxx.xxx.xxx
[80]
• 30 Day
• Daily
• Full Rate
• None
Section 3: Programming the 7847i-E
DESCRIPTION
then press the [Enter] key when prompted for the new
password and its confirmation.
This prompt is displayed if [Y] was pressed in Prompt 4 or
5.
Enter a 4-digit password (0-9, A-F, N, S, T, X, Y).
Re-enter the password as confirmation.
If the password doesn't match the first entry, the following
is displayed followed by the "Exit Prog. Mode?" prompt:
Verify Not OK
PSWD not created
Otherwise, the "Exit Prog. Mode?" prompt is displayed
directly.
Exits program mode.
Press [N] to go back to Prompt 3.
Press [ESC] to load factory defaults.
Refer to the Exiting Programming Mode paragraph in this
section.
Press the [space] key to scroll through the modes of
operation. Press [ENTER] to select ECP mode.
See Table 5 if programming other modes.
Enter the four part primary CS IP address of the receiver
at the reporting center to which this device will report.
The four parts of the address must be separated by
spaces.
NOTE: This entry CANNOT be left as 255.255.255.255". It
MUST be programmed with a valid IP address.
Enter the Central Station Port Number.
NOTE: The CS Port number must match the "Listening
Port" question of the receiver.
Select the "Only One CS IP" option, if only one Central
Station IP address is desired and go to Prompt 18: Verify
Inst. Key. Select the "Fail to CS IP2" option, if a
secondary Central Station IP address is desired.
Prompts 13-15 apply only if Prompt 12: Alarm Delivery is
set to "Fail to CS IP2".
Enter the four part secondary CS IP address of the receiver
at the reporting center to which this device will report. The
four parts of the address must be separated by spaces.
NOTE: This entry CANNOT be left as "255.255.255.255" if
using the Secondary CS IP. It MUST be programmed with
a valid IP address.
Enter the Central Station Port Number.
NOTE: The CS Port number must match the "Listening
Port" question of the receiver.
Sets the supervision timing for the secondary internet
receiver to send a test alarm if set to Daily or 30 Day, or
to send a status message to the receiver if the interval is
set to Full Rate. Selecting Full Rate means secondary
supervision will be the same as primary.
NOTE: The second receiver must be programmed to
supervise subscribers in order to generate a
communication failure.
Press the [space] key to scroll through the choices.
3-3