Mounting Location And Position - Siemens SIMATIC IPC547E Operating Instructions Manual

Hide thumbs Also See for SIMATIC IPC547E:
Table of Contents

Advertisement

Note
The device fulfills the requirements for a fire protection housing according to EN 60950-1.
Therefore, it can be installed without additional fire protection.
● Install the device only in one of the described permitted mounting positions.
● Provide adequate volume in the switchgear cabinet for air circulation and heat transport.
● Do not cover the vent slots of the device.
● Ensure that the maximum air intake temperature, measured 10 cm before the air intake
● The minimum distance between the device and the housing is 10 cm on the air output
● Install the device in such a way that it does not pose a danger, for example, by falling
3.2.2

Mounting location and position

Mounting location
The device can be mounted in control desks, switchboards and 19" rack systems, both
horizontally and vertically.
Mounting position
You can mount the device as follows:
● Mounting with mounting brackets, horizontal
● Mounting on device bases, horizontal
● Tower installation, vertical:
● Mounting on telescopic rails
SIMATIC IPC547E
Operating Instructions, 09/2013, A5E32317120-AA
Keep at least 10 cm distance between the device and switchgear cabinet.
opening, does not exceed 40° C. The maximum air intake temperature must be
accounted for especially when sizing closed switchgear cabinets.
end.
over.
You can order a Tower Kit for tower installation.
When telescopic rails are used for mounting, the device can be withdrawn fully from the
cabinet or rack. Note the information in section "Telescopic rails (Page 107)".
Installing and connecting the device
3.2 Mounting the device
31

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents