Particulate Contamination

758
G8332 Command Reference for ENOS 8.4
Attention: Airborne particulates (including metal flakes or particles) and reactive 
gases acting alone or in combination with other environmental factors such as 
humidity or temperature might pose a risk to the device that is described in this 
document.
Risks that are posed by the presence of excessive particulate levels or 
concentrations of harmful gases include damage that might cause the device to 
malfunction or cease functioning altogether. This specification sets forth limits for 
particulates and gases that are intended to avoid such damage. The limits must not 
be viewed or used as definitive limits, because numerous other factors, such as 
temperature or moisture content of the air, can influence the impact of particulates 
or environmental corrosives and gaseous contaminant transfer. In the absence of 
specific limits that are set forth in this document, you must implement practices 
that maintain particulate and gas levels that are consistent with the protection of 
human health and safety. If Lenovo determines that the levels of particulates or 
gases in your environment have caused damage to the device, Lenovo may 
condition provision of repair or replacement of devices or parts on implementation 
of appropriate remedial measures to mitigate such environmental contamination. 
Implementation of such remedial measures is a customer responsibility..
Contaminant
Limits
Particulate
• The room air must be continuously filtered with 40% atmospheric 
dust spot efficiency (MERV 9) according to ASHRAE Standard 52.2
• Air that enters a data center must be filtered to 99.97% efficiency or 
greater, using high‐efficiency particulate air (HEPA) filters that meet 
MIL‐STD‐282.
• The deliquescent relative humidity of the particulate contamination 
must be more than 60%
• The room must be free of conductive contamination such as zinc whis‐
kers.
Gaseous
• Copper: Class G1 as per ANSI/ISA 71.04‐1985
• Silver: Corrosion rate of less than 300 Å in 30 days
ASHRAE 52.2‐2008 ‐ Method of Testing General Ventilation Air‐Cleaning Devices for Removal 
Efficiency by Particle Size. Atlanta: American Society of Heating, Refrigerating and Air‐Con‐
ditioning Engineers, Inc.
The deliquescent relative humidity of particulate contamination is the relative humidity 
at which the dust absorbs enough water to become wet and promote ionic conduction.
ANSI/ISA‐71.04‐1985. Environmental conditions for process measurement and control systems: 
Airborne contaminants. Instrument Society of America, Research Triangle Park, North Car‐
olina, U.S.A.