Connecting A Field Device To Profinet - Siemens SIMATIC PCS 7 Operating Manual

Process control system
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

Downloading
To transfer the configuration and parameters, select the "<Remote I/O>" object and then select
the Device > Upload to PC/PG... menu command.
Note
The automatic detection of the <modules> depends on the type of <remote I/O>, the
<modules>, and the device description.
7.3.1.11

Connecting a field device to PROFINET

To integrate distributed I/O devices (e.g., ET 200M) or links for connecting intelligent DP or
PA field devices (e.g., IE/PB link) via PROFINET, follow these steps:
Creating a network
1. Open the process device network view in SIMATIC Manager.
2. Select the "Networks" folder in the tree structure in the left window and select the Insert
3. Click the "Assign Device Type" button.
Inserting a field device or remote I/O
Follow the steps below to insert objects into higher-level objects one after the other.
Higher-level object
"Networks" folder
PROFINET network
Header module (selection: remote I/O)
Modules (selection: module)
1. Select the higher-level object in the tree structure in the window on the right.
2. In the shortcut menu, select the menu command Insert New Object > Object.
3. In the dialog box that opens, enter the name of the process tag.
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA
New Object > Object command from the shortcut menu.
The "Insert Object" dialog box opens.
The dialog box "<... SIMATIC PDM – Insert Object(s)" opens.
Object to be inserted
Type of network via which the field devices are connected
to the automation system (e.g., PROFINET network).
Header module (selection: remote I/O)
Modules (selection: module)
Field device (selection:HART device)
Functions
7.3 Device management
97