7.3 Device management
Downloading
To transfer the configuration and parameters, select the "<Remote I/O>" object and then select
the Device > Upload to PC/PG... menu command.
Note
Slot function settings
The automatic detection of the <modules> depends on the type of <remote I/O>, the
<modules>, and the device description.
Configure lower-level objects
There may be instances where you have to assign a specific device from the catalog to an
object before you can configure lower-level objects. You have to start SIMATIC PDM for the
object to make the assignment (context-sensitive menu command "Open object").
Example:
You insert a remote I/O and assign the respective device to it, for example, an ET 200iSP
header module. Then, you configure the remote I/O module. Only after you have assigned a
HART-capable module to this module can you insert a channel and a HART device. The pre-
defined module "unused slot" cannot include HART devices or channels.
7.3.1.13

Inserting a HART device at a HART module

The integration procedure is explained using the example of a HART device on an ET 200iSP
HART module:
Inserting a HART device based on the example of an ET 200iSP HART module
1. Position an "IM152-1" you have selected from the hardware catalog under "PROFIBUS DP
2. Insert a HART module "4 AI 2WIRE HART" from the hardware catalog under
3. Place the object listed in "...\AI\4 AI 2WIRE HART\HART field device" in the detail view.
4. Assign the device type to the inserted device (device description).
7.3.1.14

Integrating an FF field device

FF devices can be configured using SIMATIC PCS 7 from PCS 7 version 8.0 Update 1.
Information on this can be found in the following documentation:
SIMATIC Process Control System PCS 7, PCS 7 - FOUNDATION Fieldbus
102
\ET 200iSP" at the DP master system.
The detail view in the table below the graphic object displays the slots of ET 200iSP.
"PROFIBUS DP\ET 200iSP\IM 152-1\AI", into a free slot.
The HART module with 4 channels is shown in the detail view.
The PDM dialog "Device selection (Reassign) (Page 79)" opens.
Help for SIMATIC PDM (V8.2)
Operating Manual, 02/2014, A5E33203676-AA