Figure 16: Popit Switch Setting Error; Figure 17: Popit Switch Setting Error - Bosch D8125 Operation And Installation Manual

Zone expansion module
Hide thumbs Also See for D8125:
Table of Contents

Advertisement

If six POPITs are assigned in programming to each of five master zones, and one POPIT has erroneous switch settings (see
Figure 16), Master Zone 5 appears to have only five POPITs installed, and Master Zone 7 (which has no POPITs assigned in
programming) appears to have one POPIT installed. Both "missing" and "extra" POPIT conditions will be displayed on the
D1252A.
PROGRAMMED
2.5 Z1POINTS
2.6 Z2POINTS
2.7 Z3POINTS
2.8 Z4POINTS
2.9 Z5POINTS
2.10 Z6POINTS
2.11 Z7POINTS
2.12 Z8POINTS
Figure 17 also displays a system containing one POPIT with erroneous switch settings. Both "missing" and "extra" POPIT
conditions will be displayed on the D1252A after entering a [Command 44].
PROGRAMMED
2.5 Z1POINTS
2.6 Z2POINTS
2.7 Z3POINTS
2.8 Z4POINTS
2.9 Z5POINTS
2.10 Z6POINTS
2.11 Z7POINTS
2.12 Z8POINTS
© 2004 Bosch Security Systems, Inc.
INSTALLED
6
MASTER ZONE 1: 6
6
MASTER ZONE 2: 6
6
MASTER ZONE 3: 6
6
MASTER ZONE 4: 6
6
MASTER ZONE 5: 5
00
00
MASTER ZONE 7: 1
00

Figure 16: POPIT Switch Setting Error

INSTALLED
6
MASTER ZONE 1: 6
6
MASTER ZONE 2: 6
6
MASTER ZONE 3: 6
6
MASTER ZONE 4: 5
6
MASTER ZONE 5: 7
00
00
00

Figure 17: POPIT Switch Setting Error

D8125 Operation and Installation Guide
Page 37
D8125
Installation
MISSING
POPIT
EXTRA
POPIT
MISSING
POPIT
EXTRA
POPIT
74-04247-000-N