Danfoss FC 300 Design Manual
Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

Advertisement

Table of Contents
loading

Summary of Contents for Danfoss FC 300

  • Page 1: Table Of Contents

    Safe Stop Installation (FC 302 and FC 301 - A1 enclosure only) Safe Stop Commissioning Test FC 300 Selection Electrical Data General Specifications Efficiency Acoustic Noise Peak Voltage on Motor Derating for Installing Long Motor Cables or Cables with Larger Cross-Sec- tion MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 2 Final Set-Up and Test Additional Connections Relay Connection Relay Output Parallel Connection of Motors Motor Thermal Protection How to Connect a PC to the FC 300 The FC 300 Software Dialog Residual Current Device Application Examples Start/Stop Pulse Start/Stop Potentiometer Reference...
  • Page 3 Relay Option MCB 105 24 V Back-Up Option MCB 107 (Option D) IP 21/IP 4X/ TYPE 1 Enclosure Kit LC Filters RS-485 Installation and Set-up RS-485 Installation and Set-up FC Protocol Overview Network Configuration MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 4 FC 300 Design Guide FC Protocol Message Framing Structure - FC 300 Examples Danfoss FC Control Profile Troubleshooting Status messages - FC 300 DG Index MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 5: How To Read This Design Guide

    FC 300 Design Guide How to Read this Design Guide How to Read this Design Guide This Design Guide will introduce all aspects of your FC 300. Available literature for FC 300 ® The VLT AutomationDrive FC 300 Operating Instructions MG.33.AX.YY provide the neccessary information for getting the drive up and running.
  • Page 6: Symbols

    Nominal motor current Nominal motor frequency Nominal motor power Nominal motor voltage Parameter par. Protective Extra Low Voltage PELV Printed Circuit Board Rated Inverter Output Current Revolutions Per Minute Second Torque limit Volts MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 7: Definitions

    The rated motor current (nameplate data). M-TYPE Size and type of the connected motor (dependencies). The rated motor speed (nameplate data). The rated motor power (nameplate data). The rated torque (motor). The instantaneous motor voltage. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 8 Voltage input, 0-10 V DC (FC 301) Voltage input, -10 - +10 V DC (FC 302). Analog Outputs The analog outputs can supply a signal of 0-20 mA, 4-20 mA, or a digital signal. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 9 The operation can be either periodic duty or none-periodic duty. The Local Control Panel (LCP) makes up a complete interface for control and programming of the FC 300 Series. The control panel is detachable and can be installed up to 3 metres from the frequency converter, i.e.
  • Page 10 ϕ1 = 1 The power factor indicates to which extent the The lower the power factor, the higher the I frequency converter imposes a load on the mains the same kW performance. supply . MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 11 + .. + In addition, a high power factor indicates that the different harmonic currents are low. The FC 300 frequency converters' built-in DC coils produce a high power factor, which minimizes the imposed load on the mains supply. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 12 FC 300 Design Guide MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 13: Introduction To Fc 300

    The FC 300 AutomationDrive DC link capacitors remain charged after power has been disconnected. To avoid an electrical shock hazard, disconnect the FC 300 from the mains before carrying out main- tenance. Wait at least as follows before doing service on the frequency converter: FC 300: 0.25 –...
  • Page 14 1997. The directive applies to all electrical equipment and appliances used in the 50 - 1000 V AC and the 75 - 1500 V DC voltage ranges. Danfoss CE-labels in accordance with the directive and issues a decla- ration of conformity upon request.
  • Page 15: Air Humidity

    Danfoss CE labels the frequency converters in accordance with the low-voltage directive. This means that if the frequency converter is installed correctly, we guarantee compliance with the low-voltage directive. Danfoss issues a declaration of conformity that confirms our CE labelling in accordance with the low- voltage directive.
  • Page 16: Vibration And Shock

    IEC/EN 60068-2-64: Vibration, broad-band ran- The frequency converter complies with require- ments that exist for units mounted on the walls and floors of production premises, as well as in panels bolted to walls or floors. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 17: Control Principle

    Short circuit behaviour on FC 301 depends on the current transducer in the positive DC link and the desaturation protection with feedback from the 3 lower IGBT's and the brake. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 18: Control Structure In Vvc

    PID control. The Speed PID control parameters are located in the par. group 7-0*. The resulting reference from the Speed PID control is sent to the motor control limited by the frequency limit. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 19: Control Structure In Flux Sensorless (Fc 302 Only)

    The Process PID parameters are found in par. group 7-2* and 7-3*. Control Structure in Flux with Motor Feedback Control structure in Flux with motor feedback configuration (only available in FC 302): MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 20: Internal Current Control In Vvc+ Mode

    When the frequency converter is at the current limit during motor operation or regenerative operation, the frequency converter will try to get below the preset torque limits as quickly as possible without losing control of the motor. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 21: Local (Hand On) And Remote (Auto On) Control

    The table shows under which conditions either the Local reference or the Remote reference is active. One of them is always active, but both can not be active at the same time. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 22 The scaling of analog references are described in par. groups 6-1* and 6-2*, and the scaling of digital pulse references are described in par. group 5-5*. Reference limits and ranges are set in par. group 3-0*. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 23: Reference Handling

    Configuration Mode is set to [3] Process. In that case the following relations between the resulting reference (after clamping) and the sum of all ref- erences is as shown to the right. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 24: Scaling Of References And Feedback

    • And both points defining the scaling graph are in the same quadrant. The size of the Dead Band is defined by either P1 or P2 as shown in the graph below. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 25 P1 = (1V, 0 RPM) will result in a -1V to +1V dead band in this case provided that the end point P2 is placed in either Quadrant 1 or Quadrant 4. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 26 FC 300 Design Guide Introduction to FC 300 Case 1: Positive Reference with Dead band, Digital input to trigger reverse This Case shows how Reference input with limits inside Min – Max limits clamps. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 27 This Case shows how Reference input with limits outside -Max – +Max limits clamps to the inputs low and high limits before addition to External reference. And how the External reference is clamped to -Max – +Max by the Reference algorithm. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 28 FC 300 Design Guide Introduction to FC 300 Case 3: Negative to positive reference with dead band, Sign determines the direction, -Max – +Max MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 29: Speed Pid Control

    The Speed PID monitors the actual RPM of the motor by using a 24V (HTL) incremental encoder In the parameter list below it is assumed that all other parameters and switches remain at their default setting. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 30 Typically a Max Torque Ripple of 3 % is acceptable. For incremental encoders the Encoder Resolution is found in either par. 5-70 (24V HTL on standard drive) or par. 17-11 (5V TTL on MCB102 Option). MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 31: Process Pid Control

    The two Flux motor control prin- ciples are specially dependant on proper Speed Control PID tuning (prior to tuning the Process Control PID) to yield their full potential. Process PID Control diagram MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 32 (speed) of less than 1.6 Hz. The low-pass filter improves steady state performance but selecting a too large filter time will deteriorate the dynamic performance of the Process PID Control. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 33 Temperature reference via potentiometer (-5-35°C, 0-10 VDC) connected to terminal 53. Temperature feedback via transmitter (-10-40°C, 4-20 mA) connected to terminal 54. Switch S202 set to ON (current input). Example of Process PID Control set-up MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 34 6) Basic PID settings Process PID Normal/Inverse 7-30 [0] Normal Process PID Anti Wind-up 7-31 [1] On Process PID start speed 7-37 300 rpm Save parameters to LCP 0-50 [1] All to LCP MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 35: Ziegler Nichols Tuning Method

    Experience has shown that the control setting according to Ziegler Nichols rule provides a good closed loop response for many SYSTEMs. The process operator can do the final tuning of the control iteratively to yield satisfactory control. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 36 Avoid placing cables with a sensitive signal level alongside motor and brake cables. Radio interference higher than 50 MHz (airborne) is especially generated by the control electronics. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 37: Emc Test Results (Emission, Immunity)

    HX - No EMC filters build in the frequency converter (600 V units only) H1 - Integrated EMC filter. Fulfil Class A1/B H2 - No additional EMC filter. Fulfil Class A2 H3 - Integrated EMC filter. Fulfil class A1/B (Enclosure type A1 only) MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 38: Emc Immunity

    1 kV/12 Ω CM Enclosure 8 kV AD — — 10 V/m — 6 kV CD AD: Air Discharge CD: Contact Discharge CM: Common mode DM: Differential mode 1. Injection on cable shield. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 39 Internal inrush, RFI, and temperature measurement circuits. Custom relays. Galvanic isolation The functional galvanic isolation (a and b on drawing) is for the 24 V back-up option and for the RS 485 standard bus interface. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 40: Earth Leakage Current

    (of the cycle time) Danfoss offers brake resistors with duty cycle of 5%, 10% and 40%. If a 10% duty cycle is applied, the brake resistors are able to absorb brake power for 10% of the cycle time. The remaining 90% of the cycle time will be used on deflecting excess heat.
  • Page 41 The resistor brake circuit resistance selected should not be higher than that recommended by Danfoss. If a brake resistor with a higher ohmic value is selected, the 160% braking torque may not be achieved because there is a risk that the frequency converter cuts out for safety reasons.
  • Page 42: Control Of Mechanical Brake

    2-21 Activate Brake Speed [RPM]. If the frequency converter is brought into an alarm condition, i.e. over-voltage situation, the me- chanical brake immediately cuts in. This is also the case during safe stop. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 43 Only one event will be evaluated at any time. If an event is evaluated as FALSE, nothing happens (in the SLC) during the present scan interval and no other events will be evaluated. This means that when the MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 44 Switching on the output between the motor and the frequency converter is fully permitted. You cannot damage the frequency converter in any way by switching on the output. However, fault messages may appear. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 45: Safe Stop Of Fc 300

    Category 0 (as defined in EN 60204-1). Type Code for FC 301 A1 with Safe Stop: FC-301PK75T4Z20H4TGCXXXSXXXXA0BXCXXXX FC 301 A1 enclosure: When Safe Stop is included in the drive position 18 of Type Code must be ei- MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 46: Safe Stop Installation (Fc 302 And Fc 301 - A1 Enclosure Only)

    Safe Stop function in accordance with the re- quirements of Safety Category 3 in EN 954-1, the related information and instructions of the FC 300 Design Guide MG.33.BX.YY must be followed! The information and instructions of the Operating In-...
  • Page 47: Safe Stop Commissioning Test

    After installation and before first operation, perform a commissioning test of an installation or application making use of FC 300 Safe Stop. Moreover, perform the test after each modification of the installation or application, which the FC 300 Safe Stop is part of.
  • Page 48 FC 300 Design Guide MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 49: Fc 300 Selection

    Enclosure IP 20 (FC 301 only) Enclosure IP 55 Weight, enclosure IP20 [kg] A1 (IP 20) 0.94 0.94 0.95 0.95 0.96 0.96 0.96 0.96 0.96 Efficiency 0.25 - 3.7 kW only available as 160% high overload. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 50 FC 300 Design Guide FC 300 Selection MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 51 FC 300 Design Guide FC 300 Selection MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 52 30W to the losses. (Though typical only 4W extra for a fully loaded control card, or options for slot A or slot B, each). Although measurements are made with state of the art equipment, some measurement inaccur- acy must be allowed for (+/-5%). MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 53: General Specifications

    Max. motor cable length, unscreened/unarmoured 300 m Max. cross section to motor, mains, load sharing and brake (see section Electrical Data in the FC 300 Design Guide MG.33.BX.YY for more information), (0.25 kW - 7.5 kW) 4 mm / 10 AWG Max.
  • Page 54 EN 954-1. For correct and safe use of the Safe Stop function follow the related information and instructions in the Design Guide. 4) FC 302 and FC 301 A1with Safe Stop only. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 55 The pulse and encoder inputs (terminals 18, 29, 32, 33) are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. 1) Pulse inputs are 29 and 33 2) Encoder inputs: 32 = A, and 33 = B 3) Terminal 29: Only FC 302 MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 56 4-6 (break), 4-5 (make) Max. terminal load (AC-1) on 4-5 (NO) (Resistive load) 400 V AC, 2 A Max. terminal load (AC-15) on 4-5 (NO) (Inductive load @ cosφ 0.4) 240 V AC, 0.2 A MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 57 Minimum ambient temperature at reduced performance - 10 °C Temperature during storage/transport -25 - +65/70 °C Maximum altitude above sea level 1000 m Derating for high altitude, see section on special conditions MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 58: Efficiency

    (1-2%). This is because the sine shape of the motor current is almost perfect at high switching frequency. Efficiency of the SYSTEM (η SYSTEM To calculate the SYSTEM efficiency, the efficiency of FC 300 Series (η ) is multiplied by the efficiency of the motor (η MOTOR η...
  • Page 59: Peak Voltage On Motor

    If the motor cable is long (100 m), the rise time and peak voltage increases. If very small motors are used without phase coil insulation, connect an LC filter to the frequency con- verter. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 60 However, the design of the frequency converter sets a limit to the motor size. Derating for Installing Long Motor Cables or Cables with Larger Cross-Section The max. cable length for FC 301: 75 m unscreened cable / 50 m screened cable MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 61 The internal tempera- ture indicates whether the switch frequency can be based on the load, the ambient temperature, the supply voltage, or the cable length. The switch frequency is set in par. 14-01. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 62 FC 300 Design Guide MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 63: How To Order

    It is possible to design an FC 300 frequency converter according to the application requirements by using the ordering number SYSTEM. For the FC 300 Series, you can order standard drives and drives with integral options by sending a type code string describing the product a to the local Danfoss sales office, i.e.:...
  • Page 64 D0: MCB 107 Ext. 24 V back-up Not all choices/options are available for each FC 301/FC 302 variant. To verify if the appropriate version is available, please consult the Drive Con- figurator on the Internet. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 65: Ordering Numbers

    1) Only IP21 / > 11 kW Options can be ordered as factory built-in options, see ordering information. For information on fieldbus and application option combatibility with older software versions , please contact your Danfoss supplier. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 66 FC 300 Design Guide How to Order MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 67 FC 300 Design Guide How to Order MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 68 15.2 A 160% 120 Hz 175Z0826 PK25 - P3K7 Compact IP 20 15.2 A 160% 120 Hz 175Z0832 When using LC filters, the switching frequency must be minimum 4.5 kHz (see par. 14-01). MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 69 60 Hz 250 W 175Z4610 LC filters for FC 300, 525 - 600 V, please contact Danfoss. When using LC filters, the switching frequency must be minimum 4.5 kHz (see par. 14-01). MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 70 FC 300 Design Guide MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 71: How To Install

    FC 300 Design Guide How to Install How to Install Mechanical Dimension MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 72 9 mm 9 mm 9 mm 9 mm 9 mm 9 mm 9 mm Max weight 2.7 kg 4.9 kg 5.3 kg 6.6 kg 7.0 kg 13.5/14.2 kg 23 kg 27 kg MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 73: Mechanical Installation

    FC 300 Design Guide How to Install Mechanical Installation Accessory Bag Find the following parts included in the FC 300 Ac- cessory Bag. FC 301/FC 302 FC 301/FC 302 FC 301/FC 302 Frame sizes A1, A2 and A3 Frame size A5...
  • Page 74 How to Install Mechanical mounting FC 300 IP20 Frame sizes A1, A2 and A3 allows side-by-side installation . Due to cooling conditions , there must be a minimum of 100 mm free air passage above and below the FC 300.
  • Page 75 The service life of the frequency converter is reduced if derating for ambient temperature is not taken into account. Field Mounting For field mounting the IP 21/IP 4X top/TYPE 1 kits or IP 54/55 units are recommended. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 76: Electrical Installation

    Cable entry has to be supported around the knockout you intend to remove. The knockout can now be removed with a strong mandrel and a hammer. Remove burrs from the hole. Mount Cable entry on frequency converter. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 77: Connection To Mains And Earthing

    Fit the two screws in the de-coupling plate, slide it into place and tighten the screws. Make sure the FC 300 is properly earthed. Connect to earth connection (terminal 95). Use screw from the accessory bag. Place plug connector 91(L1), 92(L2), 93...
  • Page 78 When disconnector is used (A5 enclosure) the PE must be mounted on the left side of the drive. Mains connection B1 and B2 (IP 21/NEMA Type1 Usually the power cables for mains are unshielded ca- and IP 55/NEMA Type12) Enclosures bles. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 79: Motor Connection

    (W) (up to 7.5 kW) and motor cable to • Connect the motor cable screen to both terminals labelled MOTOR. the decoupling plate of the FC 300 and to the metal housing of the motor. Fasten screened cable to decoupling plate with screws and washers from the acces- •...
  • Page 80 All types of three-phase asynchronous standard Y). Large motors are normally delta-connected (400/690 V, Δ/Y). Refer to the motor name plate motors can be connected to the FC 300. Normally, small motors are star-connected (230/400 V, Δ/ for correct connection mode and voltage.
  • Page 81: Fuses

    Short circuit protection : The frequency converter must be protected against short-circuit to avoid electrical or fire hazard. Danfoss recommends using the fuses mentioned below to protect service personnel or other equipment in case of an internal failure in the drive. The frequency converter provides full short circuit protection in case of a short-circuit on the motor output.
  • Page 82 L50S fuses from LITTEL FUSE may substitute L50S fuses for 240 V frequency converters. A6KR fuses from FERRAZ SHAWMUT may substitute A2KR for 240 V frequency converters. A50X fuses from FERRAZ SHAWMUT may substitute A25X for 240 V frequency converters. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 83: Access To Control Terminals

    6 pole analog I/O. USB Connection . Control Terminals (FC 302) Drawing reference numbers: 10 pole plug digital I/O. 3 pole plug RS485 Bus. 6 pole analog I/O. USB Connection . Control terminals (all enclosures) MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 84: Electrical Installation , Control Terminals

    Assembling of IP55 / NEMA TYPE 12 (A5 housing) with mains disconnector Basic Wiring Example Mount terminals from the accessory bag to the front of the FC 300. Connect terminals 18, 27 and 37 (FC 302 only) to +24 V (terminal 12/13) Default settings:...
  • Page 85: Electrical Installation , Control Cables

    If this occurs, you may have to break the screen or insert a 100 nF capacitor between screen and chassis. The digital and analog in- and outputs must be connected separately to the FC 300 common inputs (ter- minal 20, 55, 39) to avoid ground currents from both groups to affect other groups. For example, switching on the digital input may disturb the analog input signal.
  • Page 86: Motor Cables

    Keep the motor cable as short as possible to reduce the noise level and leakage currents. • Connect the motor cable screen to both the decoupling plate of the FC 300 and to the metal cabinet of the motor. •...
  • Page 87: Switches S201, S202, And S801

    S202 or S801 be careful not to use force for the switch over. It is recom- mended to remove the LCP fixture (cradle) when operating the switches. The switches must not be operated with power on the frequency convert- MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 88: Final Set-Up And Test

    Press the [Hand on] key. A progress bar indicates if the AMA is in progress. Stop the AMA during operation Press the [OFF] key - the frequency converter enters into alarm mode and the display shows that the AMA was terminated by the user. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 89 "Report Value” in the [Alarm Log] shows the last measuring sequence carried out by the AMA, before the frequency converter entered alarm mode. This number along with the description of the alarm will assist you in troubleshooting. If you contact Danfoss Service, make sure to mention number and alarm description.
  • Page 90: Additional Connections

    Dimension the cross-section of the brake cable to match the brake current. Voltages up to 975 V DC (@ 600 V AC) may occur between the terminals. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 91: Relay Connection

    04 - 05 make (normally open) 04 - 06 break (normally closed) Terminals for relay connection (≤ 7.5 kW) Terminals for relay connection (11-22 kW) (A1, A2 and A3 enclosures). (A5, B1 and B2 enclosures). MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 92: Relay Output

    The electronic thermal relay ( ETR ) of the frequency converter cannot be used as motor protection for the individual motor of SYSTEMs with parallel-connected motors. Provide further motor protection by e.g. thermistors in each motor or individual thermal relays. (Circuit breakers are not suitable as protection). MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 93: Motor Thermal Protection

    Motor Thermal Protection The electronic thermal relay in FC 300 has received the UL-approval for single motor protection, when par. 1-90 Motor Thermal Protection is set for ETR Trip and par. 1-24 Motor current, I is set to the rated motor current (see motor name plate).
  • Page 94: How To Connect A Pc To The Fc 300

    For more information, see the paragraph Switches S201, S202, and S801. Communication protocol must be set to FC MC par. 8-30. How to Connect a PC to the FC 300 To control the frequency converter from a PC, in- stall the MCT 10 Set-up Software.
  • Page 95 I the installation is not carried out according to the guideline and if unscreened cables and control wires are used, some emission requirements are not complied with, although the immunity requirements are fulfilled. See the paragraph EMC test results. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 96 FC 300 Design Guide How to Install EMC-correct electrical installation of an IP20 frequency converter. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 97 How to Install Use of EMC-Correct Cables Danfoss recommends braided screened/armoured cables to optimise EMC immunity of the control cables and the EMC emission from the motor cables. The ability of a cable to reduce the in- and outgoing radiation of electric noise depends on the transfer impedance (Z ).
  • Page 98 61. This terminal is connected to earth via an internal RC link. Use twisted- pair cables to reduce the differential mode interference between the conductors. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 99: Residual Current Device

    If RCD relays are used, you must observe local regulations. Relays must be suitable for protection of 3- phase equipment with a bridge rectifier and for a brief discharge on power-up see section Earth Leakage Current for further information. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 100 FC 300 Design Guide MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 101: Application Examples

    Terminal 37 = Safe stop (FC 302 and FC 301 A1 only) Pulse Start/Stop Terminal 18 = Par. 5-10 [9] Latched start Terminal 27= Par. 5-12 [6] Stop inverse Terminal 37 = Safe stop (FC 302 and FC 301 A1 only!) MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 102: Potentiometer Reference

    Clockwise direction means channel A is 90 electrical degrees before channel B. Counter Clockwise direction means channel B is 90 electrical degrees before A. The direction determined by looking into the shaft end. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 103: Closed Loop Drive System

    Par. 5-12 Coasting Stop, Inverse [2] Terminal 29 Output Par. 5-02 Terminal 29 Mode Output [1] Par. 5-31 Torque Limit & Stop [27] Relay output [0] (Relay 1) Par. 5-40 Mechanical Brake Control [32] MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 104: Smart Logic Control Programming

    SLC is designed to act from event sent to or generated in the FC 302. The frequency converter will then perform the pre-programmed action. SLC Application Example One sequence 1: Start – ramp up – run at reference speed 2 sec – ramp down and hold shaft until stop. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 105 Set the Smart Logic Control in par. 13-00 to ON. Start / stop command is applied on terminal 18. If stop signal is applied the frequency converter will ramp down and go into free mode. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 106 FC 300 Design Guide MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 107: How To Programme

    The Graphical and Numerical Local Control Panels The easiest programming of FC 300 frequency converters is performed by the Graphical Local Control Panel (G-LCP): It is necessary to consult FC 300 Design Guide when using Numeric Local Control Panel (N-LCP).
  • Page 108: The Lcd-Display

    Press [status] and [▼ ] for brighter display Most FC 300 parameter set-ups can be changed immediately via the control panel, unless a password has been created via par. 0-60 Main Menu Password or via par. 0-65 Quick Menu Password.
  • Page 109 LCP. The following control signals will still be active when [Hand on] is activated: • [Hand on] - [Off] - [Auto on] • Reset • Coasting stop inverse • Reversing MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 110: Quick Transfer Of Parameter Settings

    All parameter settings are now stored in the LCP indicated by the progress bar. When 100% is reached, press [OK]. Stop the motor before performing this operation. You can now connect the LCP to another frequency converter and copy the parameter settings to this frequency converter as well. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 111: Display Mode

    Par. 16-82 Fieldbus REF 1 Par. 16-84 Comm. Option STW Par. 16-85 FC Port CTW 1 Par. 16-86 FC Port REF 1 Par. 16-90 Alarm Word Par. 16-92 Warning Word Par. 16-94 Ext. Status Word MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 112: Parameter Set-Up

    Smart Logic Control. Parameter Set-Up The FC 300 Series can be used for practically all assignments, which is why the number of parameters is quite large. The series offers a choice between two programming modes - a Main Menu and a Quick Menu mode .
  • Page 113 Only display parameters selected in par. 0-20 and 10 changed parameters. par. 0-24 can be viewed. It is possible to store up • the changes made since default setting. to 120 samples in the memory for later reference. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 114 (set in par. 1-25) Set the ramping down time with reference to 3-42 Ramp1 down time nominal motor speed (set in par. 1-25) Set the site from where the reference must 3-13 Reference site work MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 115: Main Menu Mode

    The procedure for changing data is the same whether you select a parameter in the Quick menu or the Main menu mode. Press [OK] to change the selected parameter. The procedure for changing data depends on whether the selected parameter represents a numerical data value or a text value. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 116: Changing A Text Value

    Change the selected digit infinitely variably by means of the up/down navigation keys. The chosen digit is indicated by the cursor. Place the cursor on the digit you want to save and press [OK]. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 117: Changing Of Data Value , Step-By-Step

    To change the parameter value, select the indexed value and press [OK]. Change the value by using the up/down keys. Press [OK] to accept the new setting. Press [CANCEL] to abort. Press [Back] to leave the parameter. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 118: How To Programme On The Numerical Local Control Panel

    If an alarm occurs the NLCP automatically switches to status mode. A number of alarms can be displayed. Parameter copy is not possible with LCP 101 Numerical Local Control Pan- MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 119: Local Control Keys

    When a start signal is applied on the control terminals and/or the bus, the frequency converter will start. The key can be selected as Enable [1] or Disable [0] via par. 0-42 [Auto on] Key on LCP. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 120: Initialisation To Default Settings

    The frequency converter is now program- med according to default settings. When you carry out manual initialisation, you also reset serial communication, RFI filter set- tings (par. 14-50) and fault log settings. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 121: Parameter Selection - Fc

    FC 300 Design Guide How to Programme Parameter Selection Parameters for FC 300 are grouped into various parameter groups for easy selection the correct param- eters for optimized operation of the frequency converter. 0-xx Operation and Display parameters • Basic Settings, set-up handling •...
  • Page 122: Parameters: Operation And Display

    (Hz). This parameter cannot be adjusted while the Japanese motor is running. (JAPANESE) [40] Turkish (TURKISH) [41] Traditional Chinese [42] factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 123 Factory Set-up [0] cannot be changed. It contains Function: the Danfoss data set, and can be used as a data Select International [0] to set par.1-20 Motor source when returning the other set-ups to a Power units to kW and the default value of par.
  • Page 124 The par. 0-12 link set-up feature is used by Multi set-up in par. 0-10 Active Set-up. Multi set-up is factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 125 FC Port CTW 1 [1685] FC Port REF 1 [1686] Alarm Word [1690] Alarm Word 2 [1691] Warning Word [1692] factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 126 (18, 19 or 32, 33). warnings in a Hex code Feedback [Unit] [1652] Reference value from pro- grammed digital input(s). factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 127 Hex code Ext. status word [Hex] [1694] One or more status conditions in a Hex code factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 128 [70] The relation will depend on the type of unit selec- [71] ted in par.0-30, Custom Readout Unit: [72] factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 129 Quick Menu, then define the password in par. 0-65 0 - par. 0 - 32 Quick Menu Password. 0.00 factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 130 Select All to LCP [1] to copy all parameters in all Full access set-ups from the frequency converter memory to Read only the LCP memory. No access factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 131 Menu parameters. If par. 0-61 Access to Main Menu w/o Password is set to Full access [0] then this parameter will be ignored. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 132: Parameters: Load And Motor

    Select which motor control principle to employ. 305. Select U/f [0], a special motor mode, for parallel connected motors in special motor applications. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 133 Enter the nominal motor power in kW according to the motor nameplate data. The default value cor- responds to the nominal rated output of the unit. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 134 Par. 1-35 Value: Main Reactance (X ) may be adjusted to obtain Motor type dependent. optimal start performance. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 135 (par. 1-36). factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 136 1-36 Iron Loss Resistance (Rfe) Value: 1 - 10.000 Ω Size related factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 137 Flux model 2; or shift between Variable Current mode and Flux model 2. This parameter is avail- able for FC 302 only. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 138 0.0 - max. motor voltage Size related Motor size Change over 0.25 kW - 7.5 kW < 10 Hz factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 139 Generating Mode to 60%. Par. 1-66 automatically Enter the slip compensation reaction speed. A high value results in slow reaction, and a low val- factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 140 The motor rotates in the reference di- Parameters for setting special motor start fea- rection. If the reference signal equals zero (0), tures. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 141 1-81 Min Speed for Function at Stop [RPM]. the motor output speed leaps to the set value. This parameter can be used for hoist applications factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 142 1-84 Precise Stop Counter Value has been received at input terminal 29 or input terminal 33. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 143 The thermistor cut-out value is > 3 kΩ. Integrate a thermistor (PTC sensor) in the motor for winding protection. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 144 For example ETR starts Digital input 18 calculating when setup 3 is selected. For the North Digital input 19 Digital input 32 factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 145 In order to com- ply with PELV the sensor must be extra isolated. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 146: Parameters: Brakes

    The braking current is active dur- ing the time period set in par. 2-02 DC Braking Time. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 147 DC link ripple ampli- sistor (Ohm)), the DC link voltage, and the resis- tor duty time. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 148 AC brake to avoid overheating of motor wind- ings. The AC brake function is available in Flux mode only (FC 302 only). factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 149 Ensure that the mechan- ical brake has locked the load before the motor enters coast mode. See Control of Mechanical Brake section. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 150: Parameters: Reference/Ramps

    Enter the Minimum Reference. The Minimum Ref- kg/s [30] erence is the lowest value obtainable by summing kg/min [31] all references. kg/h [32] t/min [33] factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 151 (par. 5-10 to par. 5-15), the percentage (relative) value is deducted Value: -100.00 - 100.00 % 0.00% factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 152 Reference Source 3 Value: No function Analog input 53 Analog input 54 Frequency input 29 (FC 302 only) Frequency input 33 factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 153 This parameter cannot be adjusted while the mo- tor is running. 3-19 Jog Speed Value: 0 - par. 4-13 RPM 150RPM factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 154 (par. 3-42) where the deceleration torque decrea- limit set in par. 4-18. The value 0.00 corresponds ses. The larger the percentage value, the greater factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 155 Value: lower the torque jerks in the application. 0.01 - 3600.00 s. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 156 3-62. (par. 3-62) where the deceleration torque increa- ses. The larger the percentage value, the greater factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 157 1-25). Choose a ramp-up time such that the out- put current does not exceed the current limit in par. 4-18 during ramping. The value 0.00 corre- factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 158 The digital potentiometer function allows the user to increase or decrease the actual reference by adjusting the set-up of the digital inputs using the factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 159 3-90 Step Size. 3-92 Power Restore Value: factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 160: Parameters: Limits/Warnings

    Sets the torque limit for motor operation. The tor- Value: que limit is active in the speed range up to the 0 - par. 4-14 factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 161 4-19 Max Output Frequency Analog input X30-12 [14] Value: Analog input X30-12 inv [16] 0.0 - 1000.0 Hz 132.0Hz factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 162 HIGH ceeds this limit (I ), the display reads CUR- HIGH RENT HIGH. The signal outputs can be program- factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 163 Enter the upper reference limit. When the actual reference exceeds this limit, the display reads Ref High. The signal outputs can be programmed to factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 164 Some systems call for avoiding certain output speeds due to resonance problems in the system. Enter the upper limits of the speeds to be avoided. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 165: Parameters: Digital In/Out

    Value: X30/3, X30/4. X30/ are the terminals on MCB 101. Input Terminal 29 is available in FC 302 only. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 166 Torque limit & stop [27] and connect this digital output to a digital input that is configured as coast. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 167 : Select Set-up activate par. 14-10 Mains Failure. Mains select bit 0 or Select Set-up select bit 1 to factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 168 Counter A (down) [61] range. Counter B (up) [63] Counter B (down) [64] 5-11 Terminal 19 Digital Input Value: Reversing [10] factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 169 Enable / no warning The digital outputs can be programmed with these VLT running functions: Running / no warning factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 170 [29]: The brake speed is lower than the setting in par. is ready for operation and there are no 4-52. faults. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 171 TRUE, the output will go high. Otherwise, ic Action [34] Set dig. out. A low is exe- it will be low. cuted. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 172 Hand on mode (as indicated by the LED light above [Auto on]. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 173 If the Selected Event condition changes before the on- or off delay timer expires, the relay output is unaffected. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 174 (par. 5-02 =Output [1] and par. 5-13 = applicable value). This parameter is available for FC 302 only. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 175 5-60. This parameter cannot be adjusted while the mo- tor is running. Options for readout output variables: factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 176 101 is mounted in the frequency converter. Change the detected encoder rotation direction without changing the wiring to the encoder. Select factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 177 Set the output frequency transferred to the output terminal 27 when the terminal is configured as 'Bus Controlled' in par. 5-60 [45]. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 178: Parameters: Analog In/Out

    Par. 6-01 Live Zero Time-out Function ence/feedback value set in par. 6-15. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 179 This parameter cannot be adjusted while the mo- tor is running. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 180 6-44. 6-31 Term. X30/11 High Voltage Value: Par. 6-30 to 10.0 V 10.0V factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 181 Resolution on analog output is 12 bit. 6-50 Terminal 42 Output Value: No operation MCO 305 0-20 mA [52] factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 182 Holds the level of Output 42 if controlled by bus. Motor cur. 4-20 mA [133] Torque % lim. 4-20 mA [134] Torque % nom 4-20 mA [135] factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 183 (100%), calculate the percentage value as follows: desired maximum current x 100 % . 10 100 = 200 % factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 184: Parameters: Controllers

    However if the amplification is too great, tiator. Since the differential gain increases at the process may become unstable. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 185 7-21. Function: The reference signal bypasses the speed control- ler by the amount specified. This feature increases factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 186 Any change to this parameter will thus af- 0.00 - 10.00 N/A 0.01N/A fect the motor speed. When the FF factor is acti- factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 187 Enter the On Reference bandwidth. When the PID Control Error (the difference between the refer- ence and the feedback) is less than the set value of this parameter the On Reference status bit is high, i.e. =1. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 188: Parameters: Communications And Options

    If an option is in- quency until communication resumes. stalled after initial power-up, the setting of par. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 189 Select Do reset [1] to return the frequency con- verter to the original set-up following a control word time-out. When the value is set to Do reset factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 190 115200 Baud Bit 13 [13] Function: Bit 14 [14] Baud rate selection for the FC (standard) port. Bit 15 [15] factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 191 8-50 Coasting Select 8-53 Start Select Value: Value: Digital input Digital input Logic AND factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 192 8-55 Set-up Select Value: 8-9* Bus Jog Digital input Parameters for configuring the Bus Jog. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 193 8-91 Bus Jog 2 Speed Value: 0 - par. 4-13 RPM 200RPM Function: Enter the jog speed. This is a fixed jog speed ac- tivated via the serial port or fieldbus option. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 194: Parameters: Profibus

    16-30 DC Link Voltage 8-90 Bus Jog 1 Speed 16-32 Brake Energy / s 8-91 Bus Jog 2 Speed factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 195 34-50 Actual Position Displays the Profibus telegram configuration. 34-51 Commanded Position 34-52 Actual Master Position 34-53 Slave Index Position factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 196 9-45 and 9-47. The maxi- Timeout active mum buffer capacity is eight error events. The Warning 34 active factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 197 Byte 1 contains the profile number and byte 2 the version number of the profile. Store edit setup Store all set-ups factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 198 This parameter displays a list of all the defined No LCP access frequency converter parameters available for Pro- Read only fibus. 0 - 115 factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 199 This parameter displays a list of all the frequency converter parameters deviating from default set- ting. 9-94 Changed Parameters (5) Array [116] Value: No LCP access factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 200: Parameters: Devicenet Can Fieldbus

    DeviceNet Operating Instructions. Note that a change to this parameter will be exe- cuted immediately. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 201 34-21 PCD 1 Read from MCO 16-02 Reference % 34-22 PCD 2 Read from MCO 16-03 Status Word (Fixed) factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 202 Please refer to the Select On [1] to enable control via the fieldbus. DeviceNet Operating Instructions (MG.33.DX.YY) for further information. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 203 10-33 Store Always 10-3* Parameter Access Value: Parameter group providing access to indexed pa- rameters and defining programming set-up. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 204 No LCP access 0 - 0 Function: This parameter is used to configure the drive via Devicenet and build the EDS-file. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 205: Parameters: Smart Logic Control

    13-02) is TRUE. Par. 13-03 resets all SLC param- Logic rule 2 [28] eters and start programming from scratch. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 206 Alarm (trip lock) [21] See parameter group 5-3* Above feedb. high [15] for further description. Thermal warning [16] Mains out of range [17] factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 207 Value: Above I high [9] See parameter group 5-3* for Do not reset SLC further description. Reset SLC factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 208 [30] Logic rule 1 [27] Use the result of logic rule 1 in Counter B [31] the logic rule. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 209 Enter the ‘trigger level’ for the variable that is monitored by this comparator. This is an array True parameter containing comparator values 0 to 5. Running factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 210 Comparator 3 [25] Use the result of comparator 3 of FALSE in the logic rule. in the logic rule. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 211 Comporator 2 [24] and 13-44. Comporator 3 [25] AND [1] evaluates the expression [13-40] AND [13-42]. Logic rule 0 [26] factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 212 13-44. Comporator 2 [24] AND [1] evaluates the expression [13-40/13-42] Comporator 3 [25] AND [13-44]. Logic rule 0 [26] factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 213 Out of speed range [10] See parameter group Thermal warning [16] 5-3* for further description. Mains voltage out of range [17] Reversing [18] factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 214 Start timer 1 [30] the event (High = TRUE). Start timer 2 [31] Set digital output A low [32] factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 215 ‘digital output 5’ selected is high (closed). changed, it will merge with other preset reference Set digital output F high [43] - any output with ‘digital output 6’ selected is high (closed). MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 216 FC 300 Design Guide How to Programme Reset Counter A [60] - resets Counter A to zero. Reset Counter B [61] - resets Counter B to zero. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 217: Parameters: Special Functions

    4-11 until the motor is as noiseless as possible. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 218 14-11 Mains Voltage at Mains Fault Value: 150 - 600 V 342 V factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 219 Select Control card test [1] to test the analog and set, the frequency converter can be restarted. digital inputs and outputs and the +10 V control factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 220 Function: For internal sevice only. 14-3* Current Limit Control The FC 300 Series features an integral Current Limit Controller which is activated when the motor current, and thus the torque, is higher than the torque limits set in par. 4-16 and 4-17.
  • Page 221 (according to IEC 61800-3). 14-41 AEO Minimum Magnetisation This parameter is available for FC 302 only. Value: 40 - 75% factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 222 Function: Select the type of output filter connected. This pa- rameter cannot be adjusted while motor is run- ning. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 223: Parameters: Drive Information

    (par. 15-14) are used to start and stop 15-04 Over Temp's the logging conditionally. Value: 0 - 65535 factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 224 [35] Select which variables are to be logged. Digital input DI29 (FC 302 only) [36] Digital input DI32 [37] factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 225 Digital outputs (not monitored in this SW release) 15-22 Historic Log: Time Warning word Array [50] Alarm word Status word Value: 0 - 2147483647 factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 226 Time is measured in ms since frequency converter View the FC type. The read-out is identical to the start. FC 300 Series power field of the type code defini- tion, characters 1-6. 15-3* Fault Log Parameters in this group are array parameters, where up to 10 fault logs can be viewed.
  • Page 227 View the software version for the option installed Shows the ordering number for the installed op- in slot C. tions. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 228 Parameter Metadata Array [30] Value: 0 - 9999 Function: This parameter contains data used by the MCT10 software tool. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 229: Parameters: Data Read-Outs

    Master reporting the Main Actual Value. 16-0* General Status Please refer to the VLT® AutomationDrive FC 300 Parameters for reading the general status, e.g. Profibus Operating Instructions MG.33.CX.YY for a the calculated reference, the active control word, detailed description.
  • Page 230 Value shown is the torque in percent of nominal input changes value to when the data read-out torque, with sign, applied to the motor shaft. values change. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 231 Parameters for reporting the reference and feed- View the percentage load on the inverter. back input. 16-36 Inv. Nom. Current Value: 0.01 - 10000.00 A factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 232 Input 18 corresponds to the bit at the far left. ‘0’ = no signal, ‘1’ = connected signal. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 233 This parameter is available for FC 302 only. Function: View the actual value at input X30/11 of MCB 101. factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 234 For more information please refer to the relevant fieldbus manual. 16-85 FC Port CTW 1 Value: 0 - 65535 factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 235 FC 300 Design Guide How to Programme 16-94 Ext. Status Word Value: 0 - FFFF Function: Returns the extended warning word sent via the serial communication port in hex code. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 236: Parameters: Encoderinput

    17-26 SSI Data Format 17-20 Protocol Selection Value: Value: Gray Code None Binary Code HIPERFACE EnDat factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 237 The value is stated in the data sheet for resolvers tor is running. 17-52 Resolver Input Frequency Value: 2.0 - 15.0 kHz 10.0kHz factory setting display text value for use in communication via serial communication port MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 238 Select which reaction the frequency converter should take in case a fault encoder signal is de- tected. The encoder function in par. 17-61 is an electrical check of the hardware circuit in the encoder SYS- TEM. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 239: Parameter Lists

    Integer 16 Int16 Integer 32 Int32 Unsigned 8 Uint8 Unsigned 16 Uint16 Unsigned 32 Uint32 Visible String VisStr Normalized value 2 bytes Bit sequence of 16 boolean variables Time difference w/o date TimD MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 240 0-61 word [0] Full access 1 set-up TRUE Uint8 Uint1 0-65 Quick Menu Password 1 set-up TRUE Access to Quick Menu w/o Pass- 0-66 word [0] Full access 1 set-up TRUE Uint8 MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 241 1-52 [Hz] All set-ups TRUE Uint16 1-53 Model Shift Frequency All set-ups FALSE Uint16 1-55 U/f Characteristic - U All set-ups TRUE Uint16 1-56 U/f Characteristic - F All set-ups TRUE Uint16 MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 242 1-95 KTY Sensor Type [0] KTY Sensor 1 All set-ups TRUE Uint8 1-96 KTY Thermistor Source [0] None All set-ups TRUE Uint8 1-97 KTY Threshold level 80 °C 1 set-up TRUE Int16 MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 243 2-20 Release Brake Current All set-ups TRUE Uint1 2-21 Activate Brake Speed [RPM] All set-ups TRUE Uint1 2-22 Activate Brake Speed [Hz] All set-ups TRUE 2-23 Activate Brake Delay 0.0 s All set-ups TRUE Uint8 MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 244 50 % All set-ups TRUE Uint8 Ramp 3 S-ramp Ratio at Decel. 3-67 Start 50 % All set-ups TRUE Uint8 Ramp 3 S-ramp Ratio at Decel. 3-68 50 % All set-ups TRUE Uint8 MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 245 [0] Off All set-ups TRUE Uint8 3-93 Maximum Limit 100 % All set-ups TRUE Int16 3-94 Minimum Limit -100 % All set-ups TRUE Int16 3-95 Ramp Delay 1.000 N/A All set-ups TRUE TimD MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 246 4-60 Bypass Speed From [RPM] All set-ups TRUE Uint1 4-61 Bypass Speed From [Hz] All set-ups TRUE Uint1 4-62 Bypass Speed To [RPM] All set-ups TRUE Uint1 4-63 Bypass Speed To [Hz] All set-ups TRUE MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 247 Uint8 Uint3 5-65 Pulse Output Max Freq #29 All set-ups TRUE Terminal X30/6 Pulse Output Var- 5-66 iable All set-ups TRUE Uint8 Uint3 5-68 Pulse Output Max Freq #X30/6 All set-ups TRUE MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 248 5-94 Pulse Out #27 Timeout Preset 0.00 % 1 set-up TRUE 5-95 Pulse Out #29 Bus Control 0.00 % All set-ups TRUE Uint1 5-96 Pulse Out #29 Timeout Preset 0.00 % 1 set-up TRUE MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 249 6-6* Analog Output 2 6-60 Terminal X30/8 Output All set-ups TRUE Uint8 6-61 Terminal X30/8 Min. Scale 0.00 % All set-ups TRUE Int16 6-62 Terminal X30/8 Max. Scale 100.00 % All set-ups TRUE Int16 MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 250 All set-ups TRUE Uint1 7-36 Process PID Diff. Gain Limit All set-ups TRUE Uint1 7-38 Process PID Feed Forward Factor 0 % All set-ups TRUE 7-39 On Reference Bandwidth All set-ups TRUE Uint8 MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 251 [3] Logic OR All set-ups TRUE Uint8 8-9* Bus Jog Uint1 8-90 Bus Jog 1 Speed 100 RPM All set-ups TRUE Uint1 8-91 Bus Jog 2 Speed 200 RPM All set-ups TRUE MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 252 Uint1 9-91 Changed Parameters (2) All set-ups FALSE Uint1 9-92 Changed Parameters (3) All set-ups FALSE Uint1 9-93 Changed parameters (4) All set-ups FALSE Uint1 9-94 Changed parameters (5) All set-ups FALSE MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 253 1 set-up TRUE Uint16 10-39 Devicenet F Parameters All set-ups TRUE Uint32 10-5* CANopen 10-50 Process Data Config Write. 2 set-ups TRUE Uint16 10-51 Process Data Config Read. 2 set-ups TRUE Uint16 MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 254 13-43 Logic Rule Operator 2 2 set-ups TRUE Uint8 13-44 Logic Rule Boolean 3 2 set-ups TRUE Uint8 13-5* States 13-51 SL Controller Event 2 set-ups TRUE Uint8 13-52 SL Controller Action 2 set-ups TRUE Uint8 MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 255 1 set-up FALSE Uint8 14-52 Fan Control [0] Auto All set-ups TRUE Uint8 14-53 Fan Monitor [1] Warning All set-ups TRUE Uint8 14-55 Output Filter [0] No Filter 1 set-up FALSE Uint8 MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 256 Slot C1 Option SW Version All set-ups FALSE VisStr[20] 15-9* Parameter Info 15-92 Defined Parameters All set-ups FALSE Uint16 15-93 Modified Parameters All set-ups FALSE Uint16 15-99 Parameter Metadata All set-ups FALSE Uint16 MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 257 16-5* Ref. & Feedb. 16-50 External Reference All set-ups FALSE Int16 16-51 Pulse Reference All set-ups FALSE Int16 16-52 Feedback [Unit] 0.000 All set-ups FALSE Int32 16-53 Digi Pot Reference 0.00 All set-ups FALSE Int16 MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 258 FALSE Uint3 16-91 Alarm word 2 All set-ups FALSE Uint3 16-92 Warning Word All set-ups FALSE Uint3 16-93 Warning word 2 All set-ups FALSE Uint3 16-94 Ext. Status Word All set-ups FALSE MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 259 17-34 HIPERFACE Baudrate [4] 9600 All set-ups FALSE Uint8 17-6* Monitoring and App. 17-60 Encoder Positive Direction [0] Clockwise All set-ups FALSE Uint8 17-61 Encoder Signal Monitoring [0] Disabled All set-ups TRUE Uint8 MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 260 FC 300 Design Guide MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 261: Options And Accessories

    FC 300 Design Guide Options and Accessories Options and Accessories Danfoss offers a wide range of options and accessories for VLT AutomationDrive FC 300 Series. Mounting of Option Modules in Slot B The power to the frequency converter must be disconnected.
  • Page 262 If the digital inputs 7, 8 or 9 are to be switched by use of the internal 24 V power supply (terminal 9) the connection between terminal 1 and 5 which is illustrated in the drawing has to be established. Principle Diagram MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 263: Encoder Option Mcb 102

    • Encoder module MCB 102 • Enlarged LCP fixture and enlarged terminal cover The encoder option does not support FC 302 frequency converters manufactured before week 50/2004. Min. software version: 2.03 (par. 15-43) MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 264 Z inv input -Data RS485 Clock out inv. Clock out inv. Z input -Data RS485 Data in Data in Future use Data in inv. Data in inv. Future use Max. 5V on X31.5-12 MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 265: Resolver Option Mcb

    Options and Accessories Resolver Option MCB 103 MCB 103 Resolver option is used for interfacing resolver motor feedback to FC 300 Automation- Drive. Resolvers are used basically as motor feed- back device for Permanent Magnet brushless synchronous motors. When the Resolver option is ordered separately the kit includes: •...
  • Page 266 Par. 17-50 Poles Resolver data sheet Par. 17-51 Input Voltage Resolver data sheet Par. 17-52 Input Frequency Resolver data sheet Par. 17-53 Transformation Ratio Resolver data sheet Par. 17-59 Resolver Interface Enabled [1] MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 267: Relay Option Mcb 105

    The relay option does not support FC 302 frequency converters manufactured before week 50/2004. Min. software version: 2.03 (par. 15-43). ≤ 7.5 kW IMPORTANT 1. The label MUST be placed on the LCP frame as shown (UL approved). MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 268 Connect power to the frequency converter. • Select the relay functions in par. 5-40 [6-8], 5-41 [6-8] and 5-42 [6-8]. NB (Array [6] is relay 7, array [7] is relay 8, and array [8] is relay 9) MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 269 FC 300 Design Guide Options and Accessories Do not combine low voltage parts and PELV systems. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 270: Back-Up Option Mcb 107 (Option D)

    Attach the Terminal Cover and the LCP or Blind Cover. When MCB 107, 24 V back-up option is supplying the control circuit, the internal 24 V supply is au- tomatically disconnected. Connection to 24 V back-up supplier (11-22 kW). MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 271: Ip 21/Ip 4X/ Type 1 Enclosure Kit

    The frequency of the resonance noise thus corresponds to the switching frequency of the frequency converter. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 272 FC 300 Design Guide Options and Accessories For the FC 300 Series, Danfoss can supply an LC filter to dampen the acoustic motor noise. The filter reduces the ramp-up time of the voltage, the peak load voltage U and the ripple current PEAK ∆I to the motor, which means that current and voltage become almost sinusoidal.
  • Page 273: Rs-485 Installation And Set-Up

    Cable: Screened twisted pair (STP) Impedance: 120 Ohm Cable length: Max. 1200 m (including drop lines) Max. 500 m station-to-station MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 274 Use the terminator dip switch on the main control board of the frequency converter to terminate the RS-485 bus. The factory setting for the dip switch is OFF. Terminator Switch Factory Setting MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 275 FC 300 Design Guide RS-485 Installation and Set-up FC 300 Parameter Settings for Modbus Communication The following parameters apply to the RS-485 interface (FC-port): Parameter Number Parameter name Function 8-30 Protocol Select the application protocol to run on the RS-485...
  • Page 276: Fc Protocol Overview

    RS-485 Installation and Set-up FC Protocol Overview The FC protocol, also referred to as FC bus or Standard bus, is the Danfoss Drives standard fieldbus. It defines an access technique according to the master-slave principle for communications via a serial bus.
  • Page 277: Fc Protocol Message Framing Structure - Fc 300

    FC 300 Design Guide RS-485 Installation and Set-up FC Protocol Message Framing Structure - FC 300 Content of a Character (byte) Each character transferred begins with a start bit. Then 8 data bits are transferred, corresponding to a byte. Each character is secured via a parity bit, which is set at "1" when it reaches parity (i.e. when there is an equal number of 1’s in the 8 data bits and the parity bit in total).
  • Page 278 The PKE field contains two sub-fields: Parameter command and response AK, and Parameter number PNU: Bits no. 12-15 transfer parameter commands from master to slave and return processed slave responses to the master. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 279 The index is used together with the parameter number to read/write-access parameters with an index, e.g. par. 15-30 Error Code. The index consists of 2 bytes, a low byte and a high byte. Only the low byte is used as an index. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 280 Par. 4-12 Motor Speed, Low Limit has a conver- sion factor of 0.1. To preset the minimum frequency to 10 Hz, trans- fer the value 100. A conversion factor of 0.1 MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 281 The block of process words is divided into two blocks of 16 bits, which always occur in the defined se- quence. PCD 1 PCD 2 Control telegram (master⇒ Control word slave) Reference-value Control telegram (slave ⇒master) Status word Present outp. frequency MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 282: Examples

    3E8 Hex corresponds to 1000 decimal. The conversion index for par. 3-41 is -2, i.e. 0.01. Danfoss FC Control Profile Control Word According to FC Profile (Par. 8-10 = FC profile) MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 283 (par. 5-10 to 5-15) programmed to Speed up and Slow down. If Freeze output is active, the frequency converter can only be stopped by the following: • Bit 03 Coasting stop MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 284 Bit 15 = ’0’: No reversing. Bit 15 = ’1’: Reversing. In the default setting, reversing is set to digital in par. 8-54 Reversing Select. Bit 15 causes reversing only when Ser. communication, Logic or or Logic and is selected. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 285 Bit 06 = ’0’: The frequency converter is not in fault mode. Bit 06 = “1”: The frequency converter is tripped and locked. Bit 07, No warning/warning: Bit 07 = ’0’: There are no warnings. Bit 07 = ’1’: A warning has occurred. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 286 100%. Bit 15 = ’1’: One of the timers exceeds 100%. All bits in the STW are set to ’0’ if the connection between the Interbus option and the fre- quency converter is lost, or an internal communication problem has occurred. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 287 100%. Negative figures are for- matted by means of 2’s complement. The Actual Output frequency (MAV) is scaled in the same way as the bus reference. The reference and MAV are scaled as follows: MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 288 Coasting stop Bit 03 = "0" leads to a stop. When bit 03 = "1", the frequency converter can start if the other start conditions are satisfied. The selection in par. 8-50 Coasting select determines how bit 03 is linked with the corre- sponding function of the digital inputs. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 289 When bit 12 = "1", the reference value is increased. If both - slowing down and accelerating - are activated (bit 11 and 12 = "1"), slowing down has priority, i.e. the speed reference value will be reduced. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 290 Bit 15 = “1” causes reversing. Note: In the factory setting reversing is set to digital in par. 8-54 Reversing select. Bit 15 causes reversing only when Ser. communication, Logic or or Logic and is selected. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 291 Bit 05, ON 3/OFF 3 When bit 02 of the Control word is "0", then bit 05 = "0". When bit 02 of the Control word is "1", then bit 05 = "1". MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 292 When bit 15 = "0", the timers for the thermal motor protection and thermal frequency converter protec- tion have not exceeded 100%. When bit 15 = "1", one of the timers has exceeded 100%. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 293: Troubleshooting

    Alarms that are trip-locked offer additional protection, meaning that the mains supply must be switched off before the alarm can be reset. After being switched back on, the FC 300 is no longer blocked and may be reset as described above once the cause has been rectified.
  • Page 294 A trip lock is an ac- tion when an alarm occurs, which may cause dam- age to drive or connected parts. A Trip Lock situation can only be reset by a power cycling. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 295 If the intermediate circuit voltage exceeds the Mains phase loss: limit, the frequency converter trips after a time. A phase is missing on the supply side, or the Possible corrections: mains voltage imbalance is too high. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 296 (in motor operation) or the torque is higher than the value in par. 4-17 (in regenerative operation). The voltages stated are the intermediate circuit volt- age of the FC 300 with a tolerance of ± 5 %. The WARNING/ALARM 13 corresponding mains voltage is the intermediate cir- cuit voltage (DC-link) divided by 1.35...
  • Page 297 515 - The Application Orientated Control cannot Drive over temperature: recognize the E^2 Prom data If the enclosure is IP 20 or IP 21/TYPE 1, the cut- out temperature of the heat-sink is 95 C +5 MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 298 5125 - Option in slot C0: Hardware incompatible WARNING/ALARM 58 with Control board hardware AMA internal fault: 5126 - Option in slot C1: Hardware incompatible Contact your Danfoss supplier. with Control board hardware MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 299 Actual combination of control board and power board is illegal. ALARM 80 Drive Initialised to Default Value: Parameter settings are initialised to default set- ting after a manual (three-finger) reset or via par. 14-22. MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 300: Index

    Control Card, Usb Serial Communication Brake Power Control Characteristics Brake Power Monitoring Control Terminals Brake Resistor Control Terminals Brake Resistors Control Word Braking Time Control Word According To Profidrive Profile (ctw) Break-away Torque MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 301 Freq. Input #33 [hz] Disposal Instruction Frequency Drive Configurator Function At Stop Fuses Earth Leakage Current Earth Leakage Current Galvanic Isolation (pelv) Earthing General Warning Earthing Of Screened/armoured Control Ca- Graphical Display bles MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 302 Lc Filter Min Speed For Function At Stop [hz] Lc Filters Min Speed For Function At Stop [rpm] Minimum Inertia Minimum Limit Missing Motor Phase Function Moment Of Inertia Motor Angle Offset MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 303 Operating State At Power-up (hand) Quick Menu Operation Mode Quick Menu Mode Ordering Form Type Code Quick Menu Mode Ordering Numbers Quick Menu Password Ordering Numbers: Brake Resistors Quick Stop Ramp Time Ordering Numbers: Harmonic Filters MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 304 Safety Earth Connection Thermistor Scaling Of References And Feedback Torque Characteristics Screened/armoured Torque Control Serial Communication Torque Limit Generator Mode Serial Communication Trip Delay At Torque Limit Serial Communication Side-by-side Installation Smart Logic Control MG.33.B7.02 - VLT is a registered Danfoss trademark...
  • Page 305 FC 300 Design Guide Index Usb Connection Usb Connection Use Of Emc-correct Cables Variable Torque Vibration And Shock Voltage Level Vvcplus Vvcplus Vvcplus Warning Word Warning Word 2 Warnings MG.33.B7.02 - VLT is a registered Danfoss trademark...