Final checkout for AutoSet 1500

The Final Checkout needs to be performed after installation
(Chapter 2), and initialization/calibration procedures (Chapter 3)
have been completed. You should ensure that AutoSet 1500 will
properly stop the press before running parts.
You need to make a few test press runs to ensure that AutoSet 1500 is working properly and
will stop on a fault condition. You will have to load tonnage-related settings and then run a
test tool (refer to Chapter 4 (Operation) for more assistance). Here are the steps for the final
checkout:
Set a high setpoint % value using the "% High Percent Tolerance Selector" on the
AutoSet board (see location of components - Figure 2-2). For simplicity, program the
high setting at 2% ("position 1" on the selector).
Run a few parts.
Check that the press top stops and that an error condition ("HI") flashes on the AutoSet
LED display and the display flashes the strain link input(s) affected.
If AutoSet 1500 displayed a message but the press did not top stop, there is a problem in
your top stop circuit. Recheck all wiring and trace the cause of the problem. Do not
continue with this procedure until the press top stops when you trip the high setpoint.
If you got to this step, and everything is working right, clear the error message by
pressing Reset. Change the high setpoint % to a proper value.
AutoSet 1500 User Manual
CAUTION
22
Installation
Ch 2
1088500