Setting item
[Cd.6] Restart command
: Refer to Section 5.7 "List of control data" for details on the setting details.
(6) When stopped with interpolation operation, write "1: Restarts" into "[Cd.6]
Restart command" for the reference axis, and then restart.
(7) If the PLC READY signal is changed from OFF to ON while stopped, restarting
is not possible.
If restart is requested, the warning "Restart not possible" (warning code: 104)
will occur.
(8) When the machine OPR and fast OPR is stopped, the error "OPR restart not
possible" (error code: 209) will occur and the positioning cannot restarts.
(9) If any of reference partner axes executes the positioning operation once after
interpolation operation stop, the warning "Restart not possible" (warning code:
104) will occur, and the positioning cannot restarts.

[3] Control data requiring setting

Set the following data to execute restart.
Setting
value
1
Set "1: Restarts".
[4] Starting conditions
The following conditions must be satisfied when restarting. (Assemble the
required conditions into the sequence program as an interlock.)
(1) Operation state
"[Md.26] Axis operation status" is "1: Stopped".
Chapter 6 Sequence Program Used for Positioning Control
Setting details
6 - 71
Buffer memory address
QD77MS2
QD77MS16
QD77MS4
1503+100n
4303+100n
n: Axis No.-1