Installation Of The Outdoor Unit

As condensing temperature rises, evaporating temperature rises and cooling capacity drops. In order to
achieve maximum cooling capacity, the location selected for outdoor unit should fulfill the following
requirements:
• Install the condensing (outdoor) unit in a way such that the hot air distributed by the outdoor
condensing unit cannot be drawn in again (as in the case of short circuit of hot discharge air). Allow
sufficient space for maintenance around the unit.
• Ensure that there is no obstruction of air flow into or out of the unit. Remove obstacles which block air
intake or discharge.
• The location must be well ventilated, so that the unit can draw in and distribute plenty of air thus
lowering the condensing temperature.
• A place capable of bearing the weight of the outdoor unit and isolating noise and vibration.
• A place protected from the direct sunlight. Otherwise use an awning for protection, if necessary.
• The location must not be susceptible to dust or oil mist.
21
• Do not install the unit at altitude over 2000m for both indoor and outdoor.