Connecting To The Co Alarm Interface - Cisco ASR 5000 Series Installation Manual

Hide thumbs Also See for ASR 5000 Series:
Table of Contents

Advertisement

Cabling the Switch Processor Input/Output Line Card

Connecting to the CO Alarm Interface

The Central Office (CO) Alarm interface utilizes a 10-pin Molex female-connector fro interconnection with the three
normally closed dry-contact relays. These relays trigger external audio and/or visual indicators for the following three
alarm levels:
 Minor Alarm: This alarm is triggered when a high temperature is detected on a card, causing the fan tray to
switch its fans to high speed.
 Major Alarm: This alarm is triggered by a:
 Hardware failure that places a card in an off-line state
 Power filter unit failure or removal from the chassis
 Failure of one or more fans on either the upper or lower fan tray
 Fan tray failure or either fan tray assembly is removed from the chassis
 Critical Alarm: This alarm is triggered when a severe degradation in service is detected. For example, if the
system is supporting a large number of subscribers and packet processing cards are removed thus significantly
reducing the amount of available CPU and memory resources.
The CO alarm interface pinout is provided in the following figure and table.
Figure 38.
Table 37.
SPIO CO Alarm Interface Pinouts
SPIO CO Alarm Interface Pinouts
Pin
Signal
1
Major Alarm - Normally closed
2
Major Alarm - Common
3
Major Alarm - Normally open
4
Minor Alarm - Normally closed
5
Minor Alarm - Common
6
Minor Alarm - Normally open
7
Critical Alarm - Normally closed
8
Critical Alarm - Common
9
Critical Alarm - Normally open
10
Not used
Connecting to the CO Alarm Interface ▀
ASR 5000 Installation Guide ▄
119