Analog inputs
Table 9-57
16 bit value (hex.)
Overflow
Overrange
0x19B5
0x0CDA
0x066D
0x0000
0xF993
0xF326
0xE64B
Underrange
Underflow
Table 9-58
16 bit value (hex.)
Overflow
Overrange
0x1999
0x0CCC
0x0000
0xF333
0xE666
Underrange
Underflow
Table 9-59
16 bit value (hex.)
Overflow
0x0A28
0x03E8
0x01F4
0x0000
0xFE0C
0xFC18
0xF830
Underflow
NCU 7x0.3 PN, NCU 7x0.3B PN
Manual, 06/2014, 6FC5397-1EP40-5BA1
Measured values in the voltage measurement operating mode
16 bit value (dec.)
6581
3291
1645
0
-1645
-3291
-6581
Measured values in the current measurement operating mode
16 bit value (dec.)
6553
3277
0
-3277
-6553
Measured values in the "temperature measurement" operating mode
16 bit value (dec.)
2590
1000
500
0.0
-500
-1000
-2000
Connectable components
9.3 PP 72/48D 2/2A PN
Factor
-
-
0.00152
-
-
Factor
-
-
0.00305
-
-
Factor
0.1
Voltage value [V]
Deactivation
Up to 11.75 V
10 V
5 V
2.5 V
0 V
-2.5 V
-5 V
-10 V
Up to -11.75 V
Deactivation
Current value [V]
Deactivation
Up to 23.5 mA
20 mA
10 mA
0 mA
-10 mA
-20 mA
Up to -23.5 mA
Deactivation
Temperature value [V]
259 ℃
100 °C
50 ℃
0 °C
-50 ℃
-100 °C
-200 ℃
139