5. SPECIFICATIONS
5.1 General specifications
General specifications
Dielectric withstand voltage
5.2 Performance specification
Item
Analog output range
Digital input
Resolution
Total accuracy
Conversion speed
Isolation
External power supply 24V DC ±10% 200mA
Number of occupied
I/O points
Power consumption
I/O characteristics
(Default: mode 0)
Follow the procedure
described in section 8
to change
6. ALLOCATION OF BUFFER MEMORIES (BFM)
Data is transmitted between the FX
BFM
#0 E
Output mode select. Factory setting H0000
#1
Output data (Signed 16 bits binary: actual value
#2
W
11 bits + sign)
#3
#1: CH1, #2: CH2, #3: CH3, #4: CH4
#4
#5 E
Data holding mode. Factory setting H0000
#6, #7
Reserved
1) [BFM #0] Output mode select: The value of BFM #0 switches the analog output between voltage and
current on each channel. It takes the form of a 4 digit hexadecimal number. The first digit will be the
command for channel 1 (CH1), and the second digit for channel 2 (CH2) etc. The numeric values of
these four digits respectively represent the following items:
H
C H 4 C H 3 C H 2 C H 1
Switching the output mode resets the I/O characteristics to the factory-default characteristics. Refer to the
performance specifications described in section 4.
Example: H2110
2) [BFM #1, #2, #3 and #4]: Output data channels CH1, CH2, CH3, and CH4
BFM #1: Output data of CH1 (Initial value: 0)BFM #2: Output data of CH2 (Initial value: 0)
BFM #3: Output data of CH3 (Initial value: 0)BFM #4: Output data of CH4 (Initial value: 0)
Item
Centigrade
-10V DC to +10V DC (External load
resistance: 2kΩ to 1MΩ).
16 bits, binary, with sign
(Effective bits for numeric value: 11 bits
and sign bit (1 bit))
5mV (10V × 1/2000)
±1% (at full scale of +10V)
2.1ms for 4 channels (Change in the number of channels used will not change
the conversion speed.)
Photo-coupler isolation between analog and digital circuits.
DC/DC converter isolation of power from main unit.
No isolation between analog channels.
The analog block occupies 8 I/O points.
(can be either inputs or outputs)
5V, 30mA (Internal power supply from MPU or powered extension unit)
Mode 0 (Voltage
At load resistance
output: -10V to
of 10kΩ
+10V)
+ 1 0 V
A n a l o g o u t p u t
- 2 , 0 0 0
- 1 0 V
- 1 0 . 2 4 V
Command sent from the programmable
controller can change the mode. The
voltage/current output mode selected
will determine the output terminals
used.
-4DA and the main unit via buffer memories (16-bit 32-point RAM).
2N
Description
O = 0:Sets the voltage output mode (-10 V to +10 V).
O = 1:Sets the current output mode (+4 mA to 20 mA).
O = 2:Sets the current output mode (0 mA to +20 mA).
CH1
CH2 and CH3 : Current output (+4 mA to +20 mA)
CH4
Same as those for the main unit
500V AC, 1min (between all terminals and ground)
DC 0mA to +20mA (External load
resistance: 500Ω).
16 bits, binary, with sign
(Effective bits for numeric value: 10 bits)
20µA (20mA × 1/1000)
±1% (at full scale of +20mA)
Mode 1 (Current
output: +4mA to
+20mA)
+ 1 0 . 2 3 5 V
+ 2 , 0 0 0
D i g i t a l i n p u t
Mode 2 (Current
output: 0mA to
+20mA)
: Voltage output (-10 V to +10 V)
: Current output (0 mA to +20 mA)
Specification
Fahrenheit
At load resistance
of 250Ω
+ 2 0 m A
A n a l o g
o u t p u t
+ 4 m A
0
D i g i t a l i n p u t
At load resistance
of 250Ω
+ 2 0 m A
A n a l o g
o u t p u t
0
D i g i t a l i n p u t
Buffer memories marked "W" can
b e w r i t t e n t o u s i n g t h e T 0
instruction in the main unit.
The status of BFM #0, #5, and #21,
( m a r k e d E ) w i l l b e w r i t t e n t o
EEPROM, therefore the set values
will be retained even after turning
off the power.
+ 1 , 0 0 0
+ 1 , 0 0 0