No Hw But Ch On; No Display - Zanussi ULTRA+ COMBI 30 Installation And Servicing

Hide thumbs Also See for ULTRA+ COMBI 30:
Table of Contents

Advertisement

4.12 NO HW BUT CH ON

Does the display shows a "Tap symbol" when
a tap is on?
Are the flow rates correct as per Section 1.2.
Is the wiring between the PCB and the diverter
valve motor connected?
Check diverter head fully engaged and clip
secured onto waterset.
Is diverter stuck in the CH position?
Check and re-fit diverter valve actuator head.
Is Boiler DHW OK?
Change diverter valve motor

4.13 NO DISPLAY

Is there 230Vac to the boiler at L and N?
Is the wiring from the terminal block to the PCB
connected securely?
Replace the PCB?
60
SECTION 4 - FAULT FINDING
NO
Is hot and cold pipework crossed?
YES
NO
Adjust flow rates to achieve 35ºC
temp rise and check filter fitted in
YES
turbine is not blocked with debris.
NO
Reconnect wiring or
replace wiring harness if
no continuity.
YES
NO
Re-engage diverter
head and secure clip to
waterset
YES
NO
Replace PCB
YES
NO
YES
YES
NO
Supply power to the boiler
NO
Connect the wiring from the terminal block to the
PCB securely.
L
NO
Is the wiring connected
between PCB and DHW
sensor?
YES
Remove the turbine, and
check for debris in the
turbine & filter. Replace
turbine if necessary. Is
DHW OK?
NO
Replace turbine sensor
Re-connect wiring
N
Installation and Servicing
NO