Logic I/O; Table 3-1. Logic I/O Configuration - Emerson Oxymitter 5000 Instruction Manual

Oxygen transmitter with foundation fieldbus communications
Hide thumbs Also See for Oxymitter 5000:
Table of Contents

Advertisement

Instruction Manual
IB-106-350 Rev. 1.2
April 2001
3-2

LOGIC I/O

This two-terminal logic contact can be config-
ured either as a solid-state relay-activated alarm
or as a bi-directional calibration handshake sig-
nal to an IMPS 4000 or SPS 4000. The configu-
ration of this signal depends on the setting of
the IO_PIN_MODE parameter via fieldbus. The
different modes available are described in Table
3-1. The IO_PIN_MODE and IO_PIN_STATE
parameters are described in Table 3-2.
a. Alarm
When configured as an alarm, this signal
alerts you to an out-of-spec condition. The
output is 5 V in series with a 340 ohm re-
sistor. For optimum performance, Rose-
mount recommends connecting the output
to a Potter & Bromfield 3.2 mA DC relay
(P/N R10S-E1Y1-J1.0K).
Mode
0
The unit is not configured for any alarm condition.
1
The unit is configured for a Unit Alarm.
2
The unit is configured for Low O
3
The unit is configured for both a Unit Alarm and Low O
4
The unit is configured for a High AC Impedance/CALIBRATION RECOMMENDED.
5*
The unit is configured for both a Unit Alarm and a High AC Impedance/CALIBRATION
RECOMMENDED.
6
The unit is configured for both a Low O
RECOMMENDED.
7
The unit is configured for a Unit Alarm, a Low O
RECOMMENDED.
8**
The unit is configured for a calibration handshake with IMPS 4000 or SPS 4000. CALIBRATION
RECOMMENDED will initiate the calibration cycle.
9
The unit is configured for a calibration handshake. CALIBRATION RECOMMENDED will not
initiate the calibration cycle with the IMPS 4000 or SPS 4000.
*The default condition for an Oxymitter 5000 without an IMPS 4000 or SPS 4000.
**The default condition for an Oxymitter 5000 with an IMPS 4000 or SPS 4000.
3-4
Startup and Operation

Table 3-1. Logic I/O Configuration

Configuration
.
2
and High AC Impedance/CALIBRATION
2
Rosemount Analytical Inc.
Of the ten modes in Table 3-1, modes 0
through 7 are the alarm modes. The factory
default is mode 5 for Oxymitter 5000 units
without an IMPS 4000 or SPS 4000. In this
mode, the output will signal when a unit
alarm or a CALIBRATION RECOM-
MENDED indication occurs.
b. Calibration Handshake Signal
If using an optional IMPS 4000 or SPS
4000, the logic I/O must be configured for
calibration handshaking. Of the ten modes
in Table 3-1, only modes 8 and 9 are con-
figured for calibration handshaking. For an
Oxymitter 5000 with an IMPS 4000 or an
SPS 4000, the factory sets the default to
mode 8. In this mode, the logic I/O will be
used to communicate between the Oxymit-
ter 5000 and sequencer and to signal the
sequencer when a CALIBRATION REC-
OMMENDATION indication occurs.
.
2
, and a High AC Impedance/CALIBRATION
2
A Division of Emerson Process Management
Oxymitter 5000