Emerson Oxymitter 5000 Instruction Manual page 127

Oxygen transmitter with foundation fieldbus communications
Hide thumbs Also See for Oxymitter 5000:
Table of Contents

Advertisement

Alarm
Value Of
Number
DETAILED_STATUS
0
0
1
1
2
2
3
4
4
8
5
16
6
32
7
64
8
128
9
256
10
512
11
1024
12
2048
13
4096
14
8192
15
16384
16
32768
17
65536
18
131072
Transducer Block
Channel Value
1
2
3
Refer to Appendix B for instructions on how to implement these variables.
Table A-3. Unit Alarm Values
Value of BLOCK_ALARM
(see FF-903)
NONE
MECHANICAL_FAILURE
MECHANICAL_FAILURE
MECHANICAL_FAILURE
N/A
N/A
MECHANICAL_FAILURE
MECHANICAL_FAILURE
MECHANICAL_FAILURE
MECHANICAL_FAILURE
MECHANICAL_FAILURE
MECHANICAL_FAILURE
N/A
MECHANICAL_FAILURE
DATA_INTEGRITY_ERROR
N/A
CONFIGURATION_ERROR
CONFIGURATION_ERROR
CONFIGURATION_ERROR
Table A-4. I/O Channel Configuration
Process Variable
Oxygen
Case Temperature
Sensor Temperature
IB-106-350
A-5
Description
No Alarm Active
Open Thermocouple
Shorted Thermocouple
Reversed Thermocouple
Not a valid alarm
Not a valid alarm
Heater Open Circuit
High High Heater Temperature
High Case Temp
Low Heater Temperature
High Heater Temperature
Open Cell Circuit
Not a valid alarm
High AC Impedance / Cell Bad
Eeprom Parameters Corrupt
Calibration Recommended
Invalid Slope value
Invalid Cell Constant Value
Bad Calibration
XD_SCALE Units
%
ºC
ºC
A