Measuring The Insulation Resistance Before Commissioning - Siemens 1LA8 Operating Instructions Manual

Simotics tn series induction motor
Table of Contents

Advertisement

Start-up

7.2 Measuring the insulation resistance before commissioning

● Any supplementary motor monitoring devices and equipment have been correctly
● All brakes and backstops are operating correctly.
● At the monitoring devices, the values for "Warning" and "Shutdown" are set.
See also
Set values for monitoring the winding temperature (Page 84)
Setpoint values for monitoring the bearing temperature (Page 84)
Converter operation
● If the design of the motor requires connection to a particular converter type, the rating plate
● The converter is correctly parameterized. The parameterization data is specified on the
● The specified limit speed n
Cooling
● Check that the machine cooling is available for commissioning.
● The bearing insulation should be executed as shown on the plates.
7.2
Measuring the insulation resistance before commissioning
Measuring the insulation resistance and polarization index (PI) provides information on the
condition of the machine. It is therefore important to check the insulation resistance and the
polarization index at the following times:
● Before starting up a machine for the first time
● After an extended period in storage or downtime
● Within the scope of maintenance work
The following information is provided regarding the state of the winding insulation:
● Is the winding head insulation conductively contaminated?
● Has the winding insulation absorbed moisture?
As such, you can determine whether the machine needs commissioning or any necessary
measures such as cleaning and/or drying the winding:
● Can the machine be put into operation?
● Must the windings be cleaned or dried?
Detailed information on testing and the limit values can be found here:
"Testing the insulation resistance and polarization index" (Page 42)
82
connected and are functioning correctly.
will contain corresponding additional information.
rating plate of the machine. Information about the parameters is available in the operating
instructions for the converter.
is not exceeded. Limit speed n
max
is not fallen below.
min
SIMOTICS TN Series N-compact 1LA8