List of fan power control (FPC) error codes

This section details the fan power control (FPC) error codes.
• 02 : EvtLogDisabled: Event Logging Disabled sensor, Log Area Reset/Cleared was asserted.
FPC system event log is cleared.
Severity
Normal
Serviceable
Automatically notify support
User Response
1. N/A
• 03 : EvtLogDisabled: Event Logging Disabled sensor, system event log full was asserted
Warning is asserted when system event log is at least 75% full. Error is asserted when System Event Log
is 100% full.
Severity
Critical
Serviceable
Automatically notify support
User Response
Complete the following steps:
1. User should clear system event log.
• 04 : EvtLogDisabled: Event Logging Disabled sensor, system event log almost full was asserted
Warning is asserted when system event log is at least 75% full.
Severity
Warning
Serviceable
Automatically notify support
User Response
1. User should be aware that system event log is almost full. No action needed.
• 10 : FAN_Tach_1A: Fan sensor, failure event was asserted, reading value : %RPM (Threshold :
1472RPM)
Asserted when Fan tach reading is below threshold RPM.
Severity
Critical
Serviceable
Automatically notify support
User Response
Complete the following steps:
1. If error is not de-asserted after several minutes, check all ten fans are installed.
2. Reseat fan module one or two times. If error still persist, replace fan module.