The Other Cases; Check Of Outdoor Refrigerant Circuit - Mitsubishi Electric MXZ-2D33VA-E1 Service Manual

Outdoor unit
Hide thumbs Also See for MXZ-2D33VA-E1:
Table of Contents

Advertisement

The other cases

Indoor unit does not operate. (different operating models in multi system)
• When you try to run two indoor units simultaneously, one for cooling and the other for heating, the unit which transmits signal
to the outdoor unit first decides the operation mode.
• When the above situation occurs, set all the indoor units to the same mode, turn OFF the indoor units, then turn them back
ON.
• Though the top of the indoor unit sometimes gets warm, this does not mean malfunction.
The reason is that the refrigerant gas continuously flows into the indoor unit even while it is not operating.

Check of outdoor refrigerant circuit

Has the operation stopped
during pump down?
Yes
The operation has stopped to pre-
vent the diesel explosion caused by
air trapped in the refrigerant circuit.
Close the stop valve, and disconnect
the power plug or turn the power sup-
ply OFF.
CAUTION : Do not start the opera-
tion again to prevent
hazards.
OBH626H
Was the operation started with
the stop valve closed, and was
No
it opened during operation?
No
The refrigerant gas amount may be
60% or less than the normal amount.
Identify where the gas is leaking from,
and fi x the leak.
152
The unit occasionally stops when the
stop valve is opened or closed during
operation. Open the stop valve and
Yes
start the cooling operation again.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents