3-10. CHARGE CALCULATIONS

(1) Additional Refrigerant Charge (R410A: oz.)

NOTE: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calcualation.
Outdoor unit
Model
precharged
MUY-GE09NA2
1 lb. 12 oz.
MUY-GE12NA2
2 lb. 9 oz.
MUY-GE15NA2
NOTE: Calculation: X oz. = 1.62/5 oz./ft
Outdoor unit
Model
precharged
MUY-GE18NA-1
NOTE: Calculation: X oz. = 1.08/5 oz./ft
NOTE: Refrigerant piping exceeding 33 ft. requires additional refrigerant charge according to the calculation.
Model
precharged
MUY-GE24NA
NOTE: Calculation: X oz. = 2.96/5 oz./ft
Due to continuing improvement, above specification may be subject to change without notice.
MSY-GE-NA2-32
M-Series - MSY/MUY-GE-NA2 Wall-Mount Systems (August 2014)
25ft
0
(Refrigerant piping length (ft) - 25)
25
30
3 lb. 7 oz.
0
1.08
(Refrigerant piping length (ft) - 25)
Outdoor
unit
33
40
4 lb. 3 oz.
0
4.14
(Refrigerant piping length (ft) - 33)
Refrigerant piping length (one way): ft.
30ft
40ft
50ft
1.62
4.86
8.10
Refrigerant piping length (one way): ft.
40
50
60
3.24
5.40
7.56
Refrigerant piping length (one way): ft.
50
60
70
10.06
15.98
21.90
60ft
65ft
11.34
12.96
70
80
90
100
9.72
11.88
14.04
16.20
80
90
100
27.82
33.74
39.66
© 2014 Mitsubishi Electric US, Inc.