APPENDICES
Table 1.7 Synchronous control output axis error (700 to 799) list (Continued)
Control mode
Command generation axis
Error
code
750
751
754
756
757
770
Error cause
• The synchronous parameter
"[Pr.440] Cam No.
(D15062+150n)" is set to other
than 0 to 256 during
synchronous control.
• When changing the synchronous
parameter "[Pr.440] Cam No.
(D15062+150n)", the cam data
of the changed cam No. does
not exist on the cam open area
during synchronous control.
• Phase compensation amount of
cam axis is equal or lower than
the minimum value
(-2147483648), or exceeding the
maximum value (2147483647).
• The synchronous parameter
"[Pr.440] Cam No.
(D15062+150n)" switch the
control mode to speed/torque/
continuous operation to torque
control for the output axis except
0 in synchronous control.
• Switch the control mode to
speed/torque/continuous
operation to torque control for
the output axis that is executing
the synchronous control
switching function.
• The output axis synchronous
parameter "[Pr.440] Cam No.
(D15062+150n)" is set to other
than 0 during speed-torque
control.
• The "[Cd.407] Synchronous
control change command
(D15130+150n)" is set to other
than 0 to 4 at control change
request.
APP - 20
Error
Corrective action
processing
• Set a value within the range of 0
to 256.
Synchronous
control
continues by
• Specify the cam No. of an
the previous
existing cam data.
cam No.
The operation
• Set a smaller cam axis phase
is controlled
compensation advance time.
with the
• Decrease the cam axis input
minimum or
value speed.
maximum
value.
• Set the output axis to linear cam
(cam No.0) when executes the
speed-torque control during
advanced synchronous control.
The control
mode is not
switched.
• Execute the request switching to
the control mode to speed/
torque/continuous operation to
torque control after executed
synchronous control switching
function.
• Set the output axis to linear cam
Control
(cam No.0) when executes the
continues by
speed-torque control during
the linear cam
advanced synchronous control.
(cam No.0).
• Set a value within the range.
Control change
is not
requested.