Corrosion Protection Agent - Siemens simovert masterdrives Operating Instructions Manual

Motion control frequency inverter (dc-ac) chassis type
Hide thumbs Also See for simovert masterdrives:
Table of Contents

Advertisement

Available languages

Available languages

Technical Data
WARNING
11.1.3.3

Corrosion protection agent

11-18
If other antifreeze agents are used, they must be ethylene glycol
based. They must also have been approved by reputable companies in
the automotive industry (GM, Ford, Chrysler).
Example: DOWTHERM SR-1.
Concerning the electrical conductivity of the antifreeze and water
mixture, the antifreeze manufacturer's guidelines apply.
The water that is mixed with the antifreeze must strictly comply with the
defnition given in the Section "Definition of cooling water".
Use of other agents can shorten the service life.
Mixing different antifreeze agents is not permitted under any
circumstances.
We recommend the use of a corrosion protection inhibitor for the
cooling circuit, e.g. NALCO 00GE056 corrosion protection from
ONDEO Nalco (Nalco Deutschland GmbH, www.nalco.com,
D-60486 Frankfurt, Tel. +49-697934-410). Concentration of the
corrosion protection inhibitor in the cooling water 0.1 ... 0.14 %.
The cooling water should be checked 3 months after the first filling of
the cooling circuit and then once a year.
If any clouding, discoloration or bacteria are detected in the cooling
water, the cooling circuit has to be flushed out and refilled.
An inspection glass should be installed in the cooling circuit to be able
to monitor the cooling water easily.
6SE7087-6KN50
Operating Instructions
SIMOVERT MASTERDRIVES
06.2006
Siemens AG

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

Table of Contents