Technical Data
Designation
Order number 6SE70...
Rated voltage
Input
Output
Rated frequency
Input
Output
Rated current
Input
Output
DC link voltage
Rated output
[kVA]
Aux. power supply
Aux. power supply
Pulse frequency [kHz]
Derating curve
Load class II acc. to EN60146-1-1:
Base load current
Overload current
Cycle time
Overload duration
Losses, cooling, power factor
Power factor
Converter cosϕU
Efficiency η
Pulse frequency 5 kHz
Dissipated losses
[kW]
Pulse frequency 5 kHz
Cooling air required
[m³/s]
Sound pressure level, dimensions, weights
Sound pressure level [dB(A)]
Type of construction
Dimensions
[mm]
Width
Height
Depth
Weight
11-6
33-2TG 0
33-7TG 0
[V]
DC 510 to 650 (-15 % / +10 %)
3 AC 0 ... rated input voltage x 0.64
[Hz]
[A]
312
367
262
308
[V]
172...217
203...256
[V]
DC 24 (20 -30) (3.0 A without options; more with options)
[V]
AC 230 ±15 % (for the fan)
5.0 – 6.0
5.0 – 6.0
0.91 x rated output current
1)
< 0.92 ind. < 0.92 ind. < 0.92 ind.
0.98
0.98
3.60
4.50
0.41
0.41
82
82
G
G
508
508
1450
1450
460
460
[kg]
155
155
1) 6SE7035-1TJ50:
Overload current only 1.36 x rated output current
Overload duration 60 s
Cycle time
300 s
= 5 corresponds to MASTERDRIVES Motion Control
= 7 corresponds to MASTERDRIVES Motion Control Performance 2
Value
35-1TJ 0
---
0 ... 400
503
423
= rated direct voltage
278...351
5.0 – 6.0
1.6 x rated output current
300 s
30 s
0.98
5.20
0.46
79
J
800
1400
551
250
Operating Instructions
06.2006
6SE7087-6KN50
Siemens AG
SIMOVERT MASTERDRIVES